background image

ENGLISH 

8.5 

Connect pumps that are delivered without cable and/or plugs to an 

external mains switch with a minimum contact gap of 

0.12" (

3 mm

)

 in all poles. 

9. MAINTENANCE AND CLEANING

In normal operation, the pump does not require any specific maintenance, thanks to its mechanical seal lubricated in an oil chamber 

and to its sealed-for-life bearings.  The electropump must not be dismantled unless by skilled personnel in possession of the 

qualifications required by the regulations in force.  In any case, all repairs and maintenance jobs must be carried out only after having 

disconnected the pump from the power mains. 

During disassembly, pay attention to any sharp parts which could cause injury. 

Checking and changing the sealing oil

To perform this operation, slacken the six screws (45) so as to be able to remove the strainer 

cover , the strainer and the pump body (1).  Retain the O-ring (28) and the nuts (51).  Using a 

suitable spanner, unscrew the impeller retaining nut (18), holding the impeller (4) still with your 

hand.  Retain the key (17) and the sand guard (15).  Now overturn the pump with the hydraulic 

part facing upwards, unscrew and remove the drainage cap (64). 

Tilt the pump so as to let the oil flow out of the drainage hole (64) and catch it in a container. 

Analyse the oil: if you find any particles of water or abrasive materials (for example, sand) it is 

advisable to check the condition of the mechanical seal (16) and to have it changed if 

necessary (at a specialized centre).  In this case change the oil too, with about 

6oz 

170 gr of oil type MARCOL 152ESSO

Top up the oil level inside the sealing oil chamber using a special funnel inserted in the hole in 

the cap (64).  Screw the drainage cap (64) back on and perform the disassembly operations in 

inverse order to reassemble the pump after having spread a suitable amount of teflon grease 

in the seat of the sand guard (15). 

OLD OIL MUST BE DISPOSED OF AS REQUIRED BY THE REGULATIONS IN FORCE. 

10. TROUBLESHOOTING

FAULT 

CHECK (possible cause) 

REMEDY 

1. The motor does not start and

makes no noise.

A. Check that the motor is live.

B. Check the protection fuses.

C. The float switch does not allow starting.

B. If they are burnt-out, change them.

C. -Ensure that the float moves freely.

-Ensure that the float is efficient (contact the

supplier).

2. The pump does not deliver.

A. The intake grid or the pipes are blocked.

B. The impeller is worn or blocked.

C.  The check valve, if installed on the delivery pipe, is

blocked in closed position.

D. The level of the liquid is too low. When starting, the

level of the liquid must be higher than that of the

strainer.

E. The required head is higher than the pump

characteristics.

A. Remove the blockage.

B. Change the impeller or remove the blockage.

C. Check that the valve is operating correctly and 

replace it if necessary.

D.  Adjust the length of the float switch cable

(SEE THE PARAGRAPH ON "ADJUSTING

THE FLOAT SWITCH").

3. The pump does not stop.

A. The switch is not disactivated by the float.

A. -Ensure that the float moves freely.

B. -Check float efficiency (the contacts could be

damaged - contact the supplier).

4. The flow is insufficient.

A. Ensure that the intake grid is not partly blocked.

B. Ensure that the impeller or the delivery pipe are not

partly blocked or encrusted.

C. Ensure that the impeller is not worn.

D. Ensure that the check valve (if fitted) is not partly

clogged.

E. On three-phase motors, check that the direction of

rotation is correct (See the paragraph on

"CHECKING THE DIRECTION OF ROTATION").

A. Remove any blockage.

B.  Remove any blockage.

C.  Change the impeller.

D. Carefully clean the check valve.

E.  Invert the connection of two supply wires.

5. The thermal overload

protection stops the pump.

A. Check that the liquid to be pumped is not too dense

as this could cause overheating of the motor.

B. Check that the water temperature is not too high.

C. The pump is partly blocked by impurities.

D. The pump is mechanically blocked.

C. Carefully clean the pump.

D. Check whether there is rubbing between the

moving and fixed parts; check the wear of the

bearings (contact the supplier).

18

17

15

1

4

45

64

16

Fig.5 

Summary of Contents for FEKA VS

Page 1: ... INSTRUCTIONS DE MISE EN SERVICE ET D ENTRETIEN FR INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE US FEKA VS FEKA VX ...

Page 2: ...uises par les normes spécifiques en la matière Il ne faut jamais faire marcher la pompe à sec 4 INSTALLATION 4 1 Si le fond du puits où la pompe doit fonctionner est particulièrement sale il est bon de prévoir un support pour poser la pompe afin d éviter que la crépine d aspiration se bouche Fig 1 4 2 Avant de positionner la pompe s assurer que la crépine n est pas totalement ou partiellement bouc...

Page 3: ...on devra être contrôlé à chaque fois qu on effectue une nouvelle installation Il faudra procéder de la façon suivante Fig 3 1 Positionner la pompe sur une surface plate 2 Mettre la pompe en marche et l arrêter immédiatement 3 Observer attentivement le contrecoup au démarrage en regardant la pompe côté moteur Le sens de rotation est correct à savoir dans le sens des aiguilles d une montre si la cal...

Page 4: ...ECUPEREE POUR LE RECYCLAGE DANS LE RESPECT DES NORMES EN VIGUEUR 10 IDENTIFICATION DES INCONVENIENTS ET REMEDES INCONVENIENTS CONTROLES causes possibles REMEDES 1 Le moteur ne démarre pas et ne fait pas de bruit A Vérifier que le moteur est sous tension B Vérifier les fusibles de protection C L interrupteur à flotteur ne permet pas le démarrage B S ils sont grillés les remplacer C Vérifier que le ...

Page 5: ...ualifications required by the regulations in force The pump must never be allowed to run dry 4 INSTALLAZIONE 4 1 If the bottom of the well or borehole in which the pump is to operate is particularly dirty it is advisable to provide a support for the pump to sit on so as to avoid clogging of the intake grid Fig 1 4 2 Before putting the pump in position ensure that the strainer is not totally or par...

Page 6: ...ach time a new installation is made Proceed as follows Fig 3 1 Place the pump on a flat surface 2 Start the pump and stop it immediately 3 Carefully observe the kick back on starting looking at the pump from the motor side The direction of rotation is correct that is clockwise if the protection cap moves as in the drawing anti clockwise If it is not possible to check as described above because the...

Page 7: ...N FORCE 10 TROUBLESHOOTING FAULT CHECK possible cause REMEDY 1 The motor does not start and makes no noise A Check that the motor is live B Check the protection fuses C The float switch does not allow starting B If they are burnt out change them C Ensure that the float moves freely Ensure that the float is efficient contact the supplier 2 The pump does not deliver A The intake grid or the pipes ar...

Page 8: ...24 3 ft 7 4 m FEKA VS 750 31 6 ft 9 6m FEKA VS 1000 38 7 ft 11 8m FEKA VS 1200 46 ft 14 m FEKA VX 550 24 3 ft 7 4 m FEKA VX 750 31 6 ft 9 6m FEKA VX 1000 38 7 ft 11 8m FEKA VX 1200 46 ft 14 m 24 3 ft 7 4 m 31 6 ft 9 6m 38 7 ft 11 8m 46 ft 14 m 24 3 ft 7 4 m 31 6 ft 9 6m 38 7 ft 11 8m 46 ft 14 m ...

Page 9: ......

Page 10: ...lgium dwtgroup com Tel 32 2 4668353 DAB PUMPS IBERICA S L Calle Verano 18 20 22 28850 Torrejón de Ardoz Madrid Spain Info spain dwtgroup com Tel 34 91 6569545 Fax 34 91 6569676 DAB PUMPS INC 3226 Benchmark Drive Ladson SC 29456 USA info usa dwtgroup com Tel 1 843 797 5002 Fax 1 843 797 3366 OOO DAB PUMPS Novgorodskaya str 1 block G office 308 127247 Moscow Russia info russia dwtgroup com Tel 7 495...

Reviews: