6
DAAB INTERFACE CARD DB409 INSTRUCTION MANUAL
6
Revision 7
Installing the Delta VFD-EL frequency converter
• Modification of the motor winder
The following criteria must be met in order to use the DAAB motor winder with the frequency converter:
• If mechanical limit switches are used, the limit switch cams must be wider than normal.
• FAAC Nordic AB recommends using encoder-type limit switches, DB405, together with the frequency converter.
• FAAC Nordic AB recommends using a motor with a speed of 2,800 rpm.
• Programming the frequency converter
To program the frequency converter, press ENTER once to select programming mode. Select program group 00.xx to 11.xx
using the arrow keys. Press ENTER to select program group. The program arrows now switch between the different program
channels in the selected program group. Press ENTER once more at the selected program channel and select value using the
arrow keys. When you have set the desired value, press ENTER again to save the new value. When all the programming has
been done, you return to normal operation by pressing MODE until the display shows H for the output frequency concerned.
Tip: By pressing MODE once more when stepping between the program channels, you change to stepping between the
program groups instead.
• Channel settings in the frequency converter
Channel
no.
Description
Factory
setting
Modified
value
00.03
used to display the output frequency during operation after power is
switched on
01
01.00
used to set the maximum output frequency
100.0
01.03
used to set the low frequency
5.00
01.04
used to set the low frequency voltage
40.0
01.05
used to set the start frequency
1.50
01.06
used to set the start frequency voltage
30.0
02.00
used to set where the setpoint value for speed is to be taken from
03
02.01
used to set the start method
01
02.02
used to set the type of stop
01
02.04
used to block reversing
01
03.00
used to set the multifunction output
01
03.08
used to set the internal cooling fan
01
04.04
used to set the function of input MI1
00
06.01
used to set the current limit for a speed increase
200
06.02
used to set the current limit at constant speed
200
06.06
used to set the electronic overload relay
02
09.00
selects communication address: 1 for motor 1, 2 for motor 2
1
09.01
used to set transfer speed
03
09.02
used to set error handling
0
09.07
used to set time delay between messages
0