Drive unit with 2.5 m silicone cable. Depending on
the type of window, different bracket sets are
available separately.
Scope of supply
Type
ZA 35-K-BSY+(-HS)
ZA 85-K-BSY+(-HS)
ZA 105-K-BSY+(-HS) ZA 155-K-BSY+(-HS)
Supply
230 V AC, +10 % / -15 %, 50 Hz
Active power
20 W (35 W)
30W (50 W)
35 W (60 W)
45 W (75 W)
Apparent output
30 VA (45 VA)
45 VA (75 VA)
55 VA (85 VA)
70 VA (105 VA)
Nominal force
300 N
800 N
1000 N
1500 N
Nominal locking force
Max. 1400 N (VdS 2580: 1100 N; without bracket)
Service life
>20 000 double strokes
Duty cycle
30 % S2 (EN 60034-1), no continuous voltage
Housing
aluminium / polycarbonate
Ingress protection
IP 65 (“-W“ = IP 54)
Temperature range
-15 ... +75 °C (VdS 2580: - 5 ... +75 °C)
Fire stability
30 min / 300°C
Emission sound pressure LpA ≤ 51 dB(A) (≤ 60,5 dB(A))
level
Nominal stroke length *
see type plate
Additional functions *
Closing edge protection activated (3 stroke repeatings)
* programmable with software SCS and BI-BT2 via Bluetooth
All approx.
20% cut-off reserve
(temporary)
OPEN
Forces
CR
III
CR
II
CR
I
300 N
300 N
300 N
300 N
800 N
800 N
800 N
800 N
1000 N
1000 N
1000 N
800 N
1500 N
1000 N
1000 N
800 N
ZA 35
ZA 85
ZA 105 ZA 155
I
III
77mm
23mm
7,1 mm/s
5 mm/s
5 mm/s
II
Closing ranges
Technical data
C
LO
S
E
Safety notes
Operating voltage 230 V AC!
Risk of injury from electric shock!
Do not reverse L+N! Connect PE!
The BSY+ bus also operates with 230 V!
- Connection must be carried out by a certified
electrical technician
- Danger of crushing hands and fingers!
- Keep people away from the operating area of
the drive
- Keep children away from the control
- Observe pressure load diagram of the gear rack!
- Use only in dry rooms
- Suitable for indoor mounting only. Use rain
detector in the event that there is a risk of rain
- Use option "-W" if mounted outdoors!
- Use unmodified original D+H parts only
- Observe the bracket-set mounting instructions
Observe enclosed red safety note!
* only with BI-BT2 (electronically isolated due to Bluetooth)
- Rack and pinion drive for electric opening and
closing of windows and flaps in the facade and
roof area
- Operating voltage 230 V AC
- Up to 4 drives possible
- Useable for smoke extraction, D+H Euro-SHEV in
accordance with DIN EN 12101-2 as well as daily
ventilation
- Suitable for indoor mounting only
Intended use
- Microprocessor-controlled synchronous
electronics BSY+ for safe and precise
synchronous running of up to 4 drives
- Individually programmable via software SCS*
- SHEV-high speed function (fast-running feature in
OPEN-direction)
- Closing edge protection for the main closing edge
- Especially quiet motor running in ventilation mode
- Optinal with "-AS2" = protection class 2 and
"-AS3" as well as "-LS" = protection class 3
Features
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing range 3 and 2, the drive runs
"OPEN" for 10 seconds, then "CLOSE" again. If after
three attempts closing is not possible, the drive
remains in this position.
In addition, the drive is equipped with passive pinch
protection. The closing speed in closing range 2 and
1 is reduced to 5 mm/s.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
main closing edge
beside closing edge
beside closing edge
Mounting information
- Swivel radius of the drive must go free over entire
range of stroke. Otherwise, the toothed rack and
the suspension can be damaged.
- Drives with a stroke of ≥800 mm must not be moun-
ted „hung up at the bottom“ (e.g. bracket UK).
- The drive set will be full configured by factory.
The drives must be reconfigured in case of
alterations (e.g. removing of drives from existing
set or integrating a new drive) with SCS*.
- Use only drives with the same force.
- Ensure evenly load distribution on all the drives.
- Eyebolt has to be adjusted so, that the drive is
disconnected with closed flap through it’s inside
stop position damping. Brackets can be damaged
by to rigid adjustment!
500
600
800
1000
1
100
1200
1300
1400
1500
1600
0
200
400
600
800
1000
1200
1400
max. Load (N)
Stroke (mm)
durable
temporary
Pressure load diagram
Maximum pressure load of the toothed rack is not
automatically identical with maximum pressure force
of the drive!
Loads from over 1000 N to 1500 N are only briefly
permissible (e.g. to throwing off snow or with wind
loads). These may arise up to a stroke of 800 mm.
Normal operation =
fast-mode SHEV =
Running speeds and forces
~7,1 mm/s / ~9 mm/s (-HS: ~17 mm/s)
WARNING
Read all safety warnings, instructions, illustrations
and specifications provided with this product.
Failure to follow all instructions listed below may
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future
reference.