3.4
12/48
LSC 44-M4
99.823.35 1.2/06/09
Wiring Plan Staircase
M
JY (St) Y
4x2x0,6
230VAC
24VDC
JY (St) Y
2x2x0,6
JY (St) Y
2x2x0,6
JY (St) Y
2x2x0,6
JY (St) Y
4x2x0,6
key-operated
vent button
smoke
vent button
RT 43-H
smoke
vent button
RT 43-N
see cable
wiring table
to further ones
to further ones
fire
detector
contact
external control
230V 50Hz
not possible to switch off
control
panel
drive
M
Symbol
Description
L S C
4 4 - M 4
s u r f a c e
t y p e
600x600x210 (230VAC/ 24VDC)
near the lift shaft
Smoke vent button (RT 43-H/N)
surface 24 VDC circa 1,5m above
upper edge firm flooring (by customer
55mm flush socket)
Vent button 24 VDC (e.g. LT 43) circa
1,2 above upper edge firm flooring (at
flush type by others 55mm flush
socket)
230V-Power supply
Weak Current Lines
Provide for separate electric circuit.
Mark fuses.
Connecting cable
: NYM-I 3x1.5
Connecting load
: RZN 4404-M = 120 VA
Install and feed separately from supply mains.
Mark cable and terminal box red.
Drive 24 VDC at smoke vent flap in the
staircase (lines must end in flush mounted
distribution box, see symbols above).
Rain detector 24VDC (FO 1362) at the top
end of the staircase
230VAC
24VDC