SHEV-control panel
Checking of Tube Systems
- for leakages (e.g. by damages)
- for faulty connections
- for correct project planning of suction openings
- check with critical applications safe detection
with response tests apart from this check,
whether an air throughput is available on the
individual suction openings.
- The ventilator voltage can be infinitely
increased from 9V (standard) up to 13.5V in
order to increase the velocity of air flow in the
tube system in critical areas.
- If the tube system does not meet the project
planning guidelines, as described here,
because of structural facts, it must be
separately calculated by D+H for the respective
conditions.
Pipe Clamps
Smoke
suction
device
For the
of the tube system,
after tube connection at TITANUS
a type has to be used,
which
Plastic pipe clamps of type NG 23 are
used as standard for installation of the
tube system (Ø 25mm). They do not
allow linear extensions.
first clamp
does not allow linear extension.
MICRO SENS ,
®
(with high
variations
in temperature
max. 30cm)
max. 80cm
Fasten tubes with
pipe clamps without
rubber ply.
Lay tube system firmly.
It must neither hang sagging
nor must it be possible that it
is moved out of place.
Air Filter