Technical data
Type
KA 66-TW-K
Power supply
230 V AC / ±15% / 50 Hz
Performance
45 W / 75 VA
Nominal force
2x 300 N
Nominal locking force
2x 1500 N (without bracket)
Lifetime
>20 000 double strokes
Duty cycle
30 % (With cycle time 10 minutes)
Housing
Aluminium powder-coated (~RAL 9006)
Ingress protection
IP 32
(With covering stoppers delivered with bracket sets)
, optional IP 42
Temperature range
-15 ... +75 °C (VdS 2580: -5 ... +75 °C)
Fire stability
30 min / 300°C
Emission sound pressure level
LpA ≤ 70 dB(A)
Nominal stroke length *
See type plate
Additional functions *
Closing edge protection activated (3 stroke repeatings);
Locking relief activated
* Programmable with software SCS
Running speed and forces
99.823.95 2.8/02/22
99.823.95 2.8/02/22
6/16
7/16
English
English
KA 66-TW-K
KA 66-TW-K
Locking force adjustment
Ø 6 mm
=
Locking force adjustment
If factory-set locking pressure of approx. 150 N is not
sufficient to close the window, it can be infinitely
increased up to approx. 250 N.
Put in covering stopper after adjustment.
approx. 150 N
approx. 250 N
Beside closing edge
Beside
closing edge
Main closing edge
All approx. 20 % switch-off reserve (temporary)
Closing edge protection
In the "CLOSE" direction the drive has an active
protection for the main closing edge. If there is an
overload in the closing range 3 and 2, the drive runs
"OPEN" for 10 seconds, then "CLOSE" again. If after
three attempts closing is not possible, the drive
remains in this position.
In addition, the drive is equipped with passive
protection. The closing speed in closing range 2 and
1 is reduced to 5 mm/s.
Significantly greater forces can be
exerted at the secondary closing
edges. Danger of crushing hands and
fingers!
11,8 mm/s
KA
66-TW
-K: 2x 300** N
Closure Ranges
12,2 mm/s
(with tensile force (1/2 nominal load)
16,1 mm/s)
77 mm
23 mm
5 mm/s
2x 150 ...
250 N
Electrical devices, accessories, batteries and packa-
ging should be sorted for environmental-friendly
recycling. Do not dispose electrical devices and
batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for
waste electrical and electronic equipment and its
implementation into national right, electrcal devices
that are no longer usable must be collected separa-
tely and disposed of in an environmentally correct
manner.
Disposal
Declaration of Conformity
We declare under our sole responsibility that the
product described under “Technical Data” is in
conformity with the following directives:
2014/30/EU, 2014/35/EU
Technical file at:
D+H Mechatronic AG, D-22949 Ammersbek
Dirk Dingfelder
Maik Schmees
CEO
CTO
02.02.2022
If after mounting, the measure X is as bigger as
23 mm, null balance with software SCS is
neccesary.
Closure Ranges will shift in relation to new zero
point.
Mount the drives mechanical stress-free.
With that, more even load distribu-
tion is ensured on all the drive
chains.
At vertical active pulling application (e.g. for a
skylight) the forces must be rearranged by
software SCS.
Mounting information
≥ 23 mm ?
X
For option “IP 42”: the chain outlet must not point
upwards.