Once a year by a specialist company, who is 
authorized by the appliance manufacturer.

Renew test badge, keep log book.

The respective current D+H maintenance 
instruction is decisive.

D+H authorized expert companies have been 
specially trained by D+H for carrying out expertly 
this maintenance, and they get automatically the 
latest maintenance  instructions.

Maintenance

Following tests must be carried out in the course of 
maintenance:

-  Outside examination / inspection of system
  components
- Checking of all relevant power supply units
-  Functional testing of connected system
  components
-  Record of competent carrying-out of
  maintenance, and designation according to
  directions

Inspection

Regular visual inspection between maintenance by the operator or a trained person.
Immediately correct any defects.

Indicators:

Green LEDs

 in the buttons must 

illuminate

.

Yellow LEDs

 in the buttons and the control panel 

are 

not allowed to illuminate or flash

 (fault).

-  If the green LEDs do not illuminate or if the 

yellow LEDs illuminate or flash, contact After 
Sales service.

Examination:

-  Check all appliances and cable connections for 

outer damage and dirt accumulation.

-  Fire detectors, smoke vent buttons, smoke vents 

and so on must not be impaired in their function 
by goods in storage or structural changings.

Inspection and maintenance has to be carried out 
according to D+H maintenance notes. Only original 
D+H spare parts may be used. Repair is to be 
carried out exclusively by D+H.
Wipe away debris or contamination with a dry, soft 
cloth.
Do not use cleaning agents or solvents.

Repair and cleaning

Electrical devices, accessories, batteries and packa-
ging  should  be  sorted  for  environmental-friendly 
recycling.  Do  not  dispose  electrical  devices  and 
batteries into household waste!
Only for EC countries:
According the European Guideline 2012/19/EU for 
waste  electrical  and  electronic  equipment  and  its 
implementation into national right, electrcal devices 
that are no longer usable must be collected separa-
tely  and  disposed  of  in  an  environmentally  correct 
manner.

Disposal

Informations for starting

Carry out following sight and performance checks for switching-on the smoke and heat vent 
control panel.

All cables 

connected?

Factory set?

(DIP switch)

10k

Ω resistor in 

smoke vent 

button

?

End module 

2x47k

Ω 

in junction box?

Connect mains. 

LED mains lightens? 

Connect battery 

lines. Control l

ightens?

Smoke vent 

flap opens and 

closes?

All necessary moving loads connected?
Smoke vent components are line-monitored.
A malfunction is connected as alarm in delivery condition of 
control panel. The smoke vent opens self-acting and can be 
reset under special conditions only.

yes

yes

yes

yes

yes

yes

yes

Performance check alarm/reset and ventilation

yes

Partial or incomplete connection of 
components can cause malfunction. 
Check following connections: mains 230 V, 
drives, smoke vent buttons, when necessary 
fire detectors and vent buttons. 
See wiring an connection plans pages 14-15.

Delivery condition of DIP switch see page 10.

Resistor must be cramped in electric last 
button on terminal 3/8 (RT 45).
See connection plan pages 14-15.

Resistor must be cramped in last or only fire 
detector on terminal 3 and 5 (type SD-O/FD-T). 
Resistor remains in control panel between 
terminal RM "R" and "–", when no fire 
detector is connected.
See connection plan page 16.

10k

Ω resistor in fire 

detector?

yes

End module on last or only drive in junction 
box on wire „E“ orange, „a“ black, „b“ black.
See connection plan page 14.

Check line safety fuse in distribution box and 
fuse mains in control panel.

Mains still not available or line switch on "0" 
or one of fuses faulty.

Possibly change poles in drive.

no

no

no

no

no

no

no

no

Summary of Contents for CPS-B1

Page 1: ...CPS B1 99 828 32 1 4 07 21 en Table of contents Page 2 Original instructions Page 3...

Page 2: ...t 9 DIP switch settings 10 Cables for D H smoke an heat vent systems 11 Wiring plan Paragon 11 24 V Emergency supply 12 230 V Power supply 13 Connection overview 14 Connection of smoke vent buttons 15...

Page 3: ...sively by trained and experienced fitters in compliance with the technical guidelines and specifications Personal handover and training for users is included Maintenance and repair Every building oper...

Page 4: ...will start flashing A malfunction of the smoke vent system will be still indicated by the extinction of the green LED in the smoke vent button After the maintenance time is expired approx 14 to 16 mon...

Page 5: ...cisive significance for an optimal effect of the smoke and heat vent system These requirements are defined in the relevant regulations of the respective country More informations are also available un...

Page 6: ...CPS B1 99 828 32 1 4 07 21 6 24 Mount control panel sheltered and easily accessible for maintenance in proximity of drive Mounting of SHEV control panel max 5 mm not included 4x English...

Page 7: ...8 ON 1 2 3 4 5 Jumper clamp holder WAGO clamp 221 not included Jumper clamp holder WAGO clamp 243 not included Overview 4x 5x 35 mm top hat rail for extension modules up to 29 mm width Document stora...

Page 8: ...fire in immediate vicinity of the mounting place the entire smoke and heat vent system will be emergency opened under alarm conditions SHEV alarm Fault Mains existing Pictogram explanation D H window...

Page 9: ...X5 X5 1 FE Shield connection for fire detector cable X5 2 R Input fire detector triggering monitoring X5 3 Reference potential X5 4 T Input smoke vent button triggering monitoring X5 5 Reference poten...

Page 10: ...Danger of crushing The drives close automatically S1 7 Extended line monitoring of the group ON All wires to the drives are monitored in all states S1 8 Operation without battery ON The charging and...

Page 11: ...g on which also the SHEV high speed HS signal is transmitted to the drive If group DIP switch 8 is ON the group will in case of a fault automatically triggered and opens Line cable control panel detec...

Page 12: ...4 07 21 12 24 24 V Emergency supply Emergency power supply for 72 hours Use VdS approved storage batteries only CPS B1 2 5 0101 2x 12V 2 2 Ah 0 3Ah Battery type 2 CPS B1 5 0101 2x 12V 3 4 Ah 0 3Ah Bat...

Page 13: ...CPS B1 99 828 32 1 4 07 21 13 24 230 V 50 Hz Seperate electric circuit Mark fuse 230 V Power supply Funtional earth FE L N PE English...

Page 14: ...D LT X3 L Z LT 84 U SD L P OK 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6 4 7 5 OK Line T R FE K A Z S Line Control Alarm CLOSE RM X5 10kW Fault Alarm Control Line CLOSE Fault n c RT X5 10kW...

Page 15: ...1 6 4 7 5 RT 45 2 8 3 1 6 4 7 5 OK 2 8 3 1 6 4 7 5 RT 45 2 8 3 1 6 4 7 5 RT 45 Line n c Fault Line Control Alarm CLOSE Alarm Control Line Line CLOSE Fault Alarm Control Line CLOSE Fault n c 10kW 2 8 3...

Page 16: ...FE B B RS L CPS B1 RM X5 LE X6 first to penultimate fire detector last fire detector SD O 371 or FD T 271 R E P 6 EM 2 1 C 3 I N 4 OUT 5 E P 6 EM 2 1 C 3 I N 4 OUT 5 10 kW T R FE K A Z S CPS B1 RM X5...

Page 17: ...netic clamps Magnetic clamps 24V max 250 mA overall power No output voltage during power failure Cutout button Magnetic clamps B B RS L CPS B1 LE X6 B B RS L CPS B1 LE X6 1 Control Panel 2 Control Pan...

Page 18: ...mplete connection of components can cause malfunction Check following connections mains 230 V drives smoke vent buttons when necessary fire detectors and vent buttons See wiring an connection plans pa...

Page 19: ...ot allowed to illuminate or flash fault If the green LEDs do not illuminate or if the yellow LEDs illuminate or flash contact After Sales service Examination Check all appliances and cable connections...

Page 20: ...English click OK RAUCHABZUG OK OK RT OK RT OK RT Operation Release in case of alarm External control Manual opening by smoke vent button Automatic opening by fire detector Automatic opening by extern...

Page 21: ...e see DIP switch S1 3 page 10 Emergency closing in case of non resettable alarm With manual release In case of automatic release by fire detector or external control External control or Operation Clos...

Page 22: ...ain Do not ventilate via smoke vent button because otherwise there would be a danger of damage by wind or water The weather automatic can be switched off via an optional automatic switch if gap ventil...

Page 23: ...CPS B1 99 828 32 1 4 07 21 23 24 English...

Page 24: ...28 32 Germany 22949Ammersbek 49 239 Tel 40 605 65 49 Fax 40 605 65 254 E Mail info dh partner com www dh partner com 99 828 32 1 4 07 21 2021 D H Mechatronic AG Ammersbek Rights to technical modifica...

Reviews: