CPS-B1
CPS-B1
99.828.32 1.4/07/21
99.828.32 1.4/07/21
10/
24
11/
24
DIP switch settings
Delivery state
ON
1
2
3
4
5
6
7
8
ON
1
2
3
4
5
DIP switch S1
S1.1
Line fault = alarm
ON
In case of a line fault (e.g. at an interrupted detector line or short circuit) the control
panel will be switched on alarm, that means the smoke vent opens.
S1.2
Group fault = alarm
ON
In case of a group fault (e.g. in case of an interrupted monitoring line) the control panel
will be switched on alarm, that means the smoke vent opens.
DIP switch must be on ON in conjunction with a ground in thermal maximal detector
(e.g. THE4).
S1.3
Deactivate remote reset detector line
ON
Smoke detector alarm can not be reset by single pressing on the button "close SHEV"
in the smoke vent button.
OFF Smoke detector alarm will be reset by pressing on the button "close SHEV" in the
smoke vent button.
S1.4
Closing group in case of alarm
ON
In case of power failure the drives will close.
S1.5
SHEV retriggering
ON
The smoke vent is triggered for a duration of 30 minutes in intervals of 2 minutes
according to VdS 2581.
S1.6
Power failure "CLOSE"
ON
In case of power failure the drives will close automatically.
Caution: Danger of crushing! The drives close automatically.
S1.7
Extended line monitoring of the group
ON
All wires to the drives are monitored in all states.
S1.8
Operation without battery
ON
The charging and monitoring of the batteries is deactivated.
DIP switch S2
S2.1
Storage operation OPEN
ON
Drives OPEN up to final position by single pressing on vent button.
OFF Drives are opening only so long as the vent button is pressed.
S2.2
Storage operation CLOSE
ON
Drives CLOSE up to final position by single pressing on vent button
OFF Drives are closing only so long as the vent button or the button "close SHEV" in the
smoke vent button is pressed.
S2.3
Ventilation time limitation
ON
The drives will automatically close again after the ventilation time set (Factory setting:
10 min., adjustable via SCS software)
Caution: Danger of crushing! The drives close automatically.
S2.4
Reset with alarm pending
ON
A permanently present alarm on the RM line or the FAS input can be suppressed by a
reset. If such an alarm is still present after a reset, the red LED in the smoke vent
button flashes to indicate that it is being suppressed.
S2.5
Lamp test
ON -
OFF
Actuate the DIP switch (ON/ OFF). All LEDs on the motherboard are switched on
continuously for 10 seconds (except for the mains OK LED, which is lit as long as the
mains voltage is present).
Line lenghts and cross sections
0,5
240
400
1
120
200
1,5
80
130
2
60
100
2,5
48
80
3
40
65
3,5
34
55
4
30
50
m
m
Total current
3 x 1,5 mm²
3 x 2,5 mm²
5
24
40
Cables for D+H smoke an heat vent systems
When selecting and installing the cables, the
regional electrical installation regulations
concerning wiring systems and the necessary
safety equipment, or guidelines on integrity
maintenance of electric lines are observed (e.g.
MLAR).
Notice:
No type designation is given for these cables,
because of a large variety on the market.
Please consult your D+H partner.
Wiring plan (Paragon)
Cross section (mm²) =
Cable lenght (m) x Total current
80
Group cable (control panel - drive)
At least three wire design:
- 2 wires for the supply of the drive
- 1 wire for line monitoring, on which also the
SHEV high speed (HS) signal is transmitted to the
drive. If group DIP switch 8 is ON, the group will in
case of a fault automatically triggered and opens.
Line cable (control panel - detector)
The cables are monitored for short circuit and for
interruption. If line DIP switch S1.1 is ON, the
group will in case of a fault automatically triggered
and opens.
230 V, 50 Hz
Seperate electric circuit.
Mark fuse.
to further ones
see line lenghts and cross sections
Drive at smoke
vent opening
SHEV control panel
Vent button
approx. 1,2 m
above upper edge
firm flooring
Smoke vent button
approx. 1,5 m above
upper edge firm flooring
External control
4x 0,8 Ø
6x 0,8 Ø (RT 45)
10x 0,8 Ø (RT 45-LT)
6x 0,8 Ø (RT 45)
10x 0,8 Ø (RT 45-LT)
2x 0,8 Ø
2x 0,8 Ø
OK
OK
Wind rain sensor
3x 0,8 Ø
System voltage 24 V!
Do not run cables with together power lines!
In case of a cable with ground wire (green /
yellow) this must not be used!
Cable and terminal boxes have to be labeled.
Fire detector
SD-O 371 or FD-T 271
English
English