![CyberPower SM180KMFX User Manual Download Page 69](http://html1.mh-extra.com/html/cyberpower/sm180kmfx/sm180kmfx_user-manual_2702909069.webp)
61
SM 180-600 KMFX User Manual
Chapter 6 Product Specification
Chapter 6 Product Specification
This chapter provides the specifications of the product, including environmental
characteristics mechanical characteristics and electrical characteristics.
6.1 Applicable Standards
The UPS has been designed to conform to the following European and international
standards:
Table 6.1 Compliance with European and International Standards
Item
Normative reference
General safety requirements for UPS
used in operator access areas
EN50091-1-1/IEC62040-1-1/AS 62040-1-1
Electromagnetic
compatibility
(EMC)
requirements for UPS
EN50091-2/IEC62040-2/AS 62040-2
(
C3
)
Method of specifying the performance
and test requirements of UPS
EN50091-3/IEC62040-3/AS 62040-3
(
VFI SS
111
)
Note
The above mentioned product standards incorporate relevant compliance clauses with generic
IEC and EN standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity
(IEC/EN/ AS61000 series) and construction (IEC/EN/AS60146 series and 60950).
6.2 Environmental Characteristics
Table 6.2 Environmental Characteristics
Item
Unit
Requirements
180kVA
300kVA
600kVA
Acoustic noise level
at 1 meter
dB
65dB @ 100% load, 62dB @ 45% load
≤70dB
Altitude of Operation
m
≤1000,load derated 1% per 100m from 1000m to 2000m
Relative Humidity
%
0-95,non condensing
Operating Temperature
℃
0-40(for UPS only),Battery life is halved for every 10°C
increase above 20°C
UPS Storage Temperature
℃
-40-70
6.3 Mechanical Characteristic
Table 6.3 Mechanical Characteristics for Cabinet
Item
Unit
180kVA
300kVA
600kVA
Mechanical
Dimension (W*D*H)
mm
600*1100*1600
600*1100*2000
2000*1100*2000
Weight
kg
170
220
660
Color
N/A
Black
Protection Level
,
IEC60529
)
N/A
IP20
Summary of Contents for SM180KMFX