Chapter 3 LCD Panel
46
SM 180-600 KMFX User Manual
Enable the switch for powering off the Power Module by touching the icon
.
Reset Battery History Data
Reset the battery history data by touching the icon
, the history data
includes the
times of discharge, days for running and hours of discharging.
Reset Dust filter Using Time
Reset the time of dust filter using by touching the icon
, it includes the days of
using and maintenance period.
TEST COMMAND
Battery Test
By touching the icon
,
the system transfer to the Battery mode to test the condition
of the battery. Ensure the bypass is working normally and the capacity of the battery is no
less than 25%.
Battery Maintenance
By touching the icon
, the system transfers to the Battery mode. This function is
used for maintaining the battery, which requires the normality of the bypass and minimum
capacity of 25% for the battery.
Battery Boost
By touching the icon
, the system starts boost charging.
Battery Float
By touching the icon
, the system starts float charging.
Stop Test
By touching the icon
, the system stops battery test or battery maintenance.