Chapter 2 Installation Instruction
19
SM 180-600 KMFX User Manual
2.6 Power Cables
2.6.1 Specifications
The UPS power cables are recommended in Table 2.2.
Table 2.2 Recommended cables for power cables
Contents
150/25
180/30
250/25
300/30
500/25
600/30
Main Input
Cable
(mm²)
A
70
95
150
185
2*150
2*185
B
70
95
150
185
2*150
2*185
C
70
95
150
185
2*150
2*185
N
70
95
150
185
2*150
2*185
Output
Cable
(mm²)
A
70
70
120
150
2*120
2*150
B
70
70
120
150
2*120
2*150
C
70
70
120
150
2*120
2*150
N
70
70
120
150
2*120
2*150
Bypass
Input
(Optional)
Cable
(mm²)
A
70
70
120
150
2*120
2*150
B
70
70
120
150
2*120
2*150
C
70
70
120
150
2*120
2*150
N
70
70
120
150
2*120
2*150
Battery
Cable
(mm²)
+
95
95
185
240
2*185
2*240
-
95
95
185
240
2*185
2*240
N
95
95
185
240
2*185
2*240
PE
Cable
(mm²)
PE
70
70
95
95
120
120
Note
The recommended cable section for power cables are only for situations described below
:
Ambient temperature
:
30
℃
.
AC loss less than 3%
,
DC loss less than 1%
,
The length of the AC power cables are no
longer than 50 m and the length of the DC power cables are no longer than 30 m.
Currents listed in the table are based on the 380V system (Line-to-line voltage) .For 400 V
system, the currents is 0.95 times and for the 415V system the current is 0.92 times.
The size of neutral lines should be 1.5~1.7 times the value listed above when the
predominant load is non-linear.
2.6.2 Specifications for Power Cables Terminal
Specifications for power cables connector are listed as Table 2.3.
Table 2.3 Requirements for power module terminal
Model
Terminal
Connection
Bolt
Bolt Aperture
Torque
6-slot cabinet
Main Input
Cables crimped
OT terminal
M10
/
15Nm
Bypass Input
Cables crimped
OT terminal
M10
/
15Nm
Battery
Cables crimped
OT terminal
M10
/
15Nm
Output
Cables crimped
OT terminal
M10
/
15Nm
PE
Cables crimped
OT terminal
M10
/
15Nm
10-slot cabinet
Main Input
Cables crimped
OT terminal
M12
13mm
22Nm
Bypass Input
Cables crimped
OT terminal
M12
13mm
22Nm