OPERATION INSTRUCTIONS FOR LCD MODULE

 

 

 

8

 

 

LCD EVENT LOG

 

5 Event Logs of UPS can be recorded. 

1. 

Press the “

ENTER

” button to activate the “

MAIN MENU

”. 

2. 

Press 

the “

” and “

” buttons to scroll to the “

Event Log

” option. 

3. 

Press the “

ENTER

” button to select the “

Event Log

” submenu. 

4. 

Press 

the “

” and “

” buttons to scroll through the “

Event Log

” submenu in the following table. 

5. 

Press 

the “

ESC

” button to return to UPS Status. 

Event Log Submenu 

Description 

(X) 

XXDXXHXXM (without PowerPanel®  Business or RMCARD) 

- - / - -    - -:- - (with PowerPanel®  Business or RMCARD) 

Event Content

 

 

MULTI-LANGUAGE INTERFACE

 

Users can configure 1 of the 4 available languages for display.   

([

English

], [

Españ ol-Spanish

], [

Français-French

], [

Deutsch-German

]) 

1. 

Press the “

ENTER

” button to activate the “

MAIN MENU

”. 

2. 

Press the 

” and “

” buttons to scroll to the “

Configure

” option. 

3. 

Press the “

ENTER

” button to select the “

Configure

” submenu. 

4. 

Press 

the “

” and “

” buttons to scroll through the “

Language

” options. 

5. 

Press the “

ENTER

” button to select the “

Language

” submenu. 

6. 

Press 

the “

” and “

” buttons to scroll to the language that you want to select.   

You may be 

prompted to save the selection, if so press the “

ENTER

” button to save the setting. 

7. 

Press 

the “

ESC

” button to cancel or return to previous LCD menu. 

 

LCD SETTINGS CONFIGURATION

 

There are 25 UPS settings that can be configured by the user. 

1. 

Press the “

ENTER

” button to activate the “

MAIN MENU

”. 

2. 

Press the 

” and “

” buttons to scroll to the “

Configure

” option. 

3. 

Press the “

ENTER

” button to select the “

Configure

” submenu. 

4. 

Press the 

” and “

” buttons to scroll to the “

Configure

” submenu in the following table. 

5. 

Press the “

ENTER

” button to select the setting you want to configure. 

The first configuration parameter will be displayed on the second column of LCD screen. 

6. 

Press 

the “

” and “

” buttons to scroll through the different parameters. 

7. 

Press the “

ENTER

” button to select the parameter you want to change. 

You may be prompted to save the selection, if so press the “

ENTER

” button to save the setting. Some options are saved 

and started automatically. (See the following table for additional details.) 

8. 

Press 

the “

ESC

” button to cancel or return to the previous LCD menu.

 

Summary of Contents for OL1000EXL

Page 1: ...User s Manual OL1000EXL OL1500EXL OL2000EXL OL3000EXL Cyber Power Systems Inc www cyberpower com K01 0000358 03 ...

Page 2: ... carry out installations CAUTION Do not unplug the unit from AC Power during operation as this will invalidate the protective ground insulation CAUTION To avoid electric shock turn off and unplug the unit before installing the input output power cord with a ground wire Connect the ground wire prior to connecting the line wires CAUTION Do not use an improper size power cord as it may cause damage t...

Page 3: ...lled indoor area free of conductive contaminants Do not install this UPS where excessive moisture or heat is present Please see specifications for acceptable temperature and humidity range CAUTION Never install a UPS or associated wiring or equipment during a lightning storm CAUTION Do not work alone under hazardous conditions CAUTION In case of the risk of electric shock do not remove the top cov...

Page 4: ...lephone fax machine or network device 5 Press the ON OFF switch to turn the UPS on The Power On indicator light will display when activated If an overload is detected an audible alarm will sound and the UPS will continuously emit two beeps per second For resetting the unit unplug some equipment from the outlets Make sure your equipment carries a load current within the unit s safe range refer to t...

Page 5: ...he power supply to equipment connected to NONCRITICAL outlets after a designated period of time 7 Serial Port Serial port provides communication between the UPS and the computer The UPS can control the computer s shutdown during a power outage through the connection while the computer can monitor the UPS and alter its various programmable parameters 8 USB port This is a connectivity port which all...

Page 6: ...Copyright 2017 Cyber Power Systems Inc BASIC OPERATION 5 OL1000EXL OL1500EXL OL2000EXL OL3000EXL ...

Page 7: ...Y Red Battery will soon need to be replaced due to insufficient runtime LCD SCREEN UPS STATUS LCD Screen UPS Status Description Line Mode UPS is operating in Line Mode Battery Mode UPS is operating in Battery Mode Bypass Mode UPS is operating in Bypass Mode Manual Bypass UPS is operating in Manual Bypass ECO Mode UPS is operating in ECO Economy Mode BUTTON OPERATION Button Operation Description ON...

Page 8: ...ays the Input Voltage I P Freq XX XHz Displays the Input Frequency O P Load XXX Displays the Output Load as a Percentage of Maximum load O P Amp X XA Displays the Output Current O P Watt XXXXXW Displays the Output Wattage O P VA XXXXXVA Displays the Output VA Load Energy XXXX XKWh Display UPS Load Energy Consumption BAT Volt XXX XV Displays the Battery Voltage BAT Cap XXX Displays the Estimated Pe...

Page 9: ... button to select the Language submenu 6 Press the and buttons to scroll to the language that you want to select You may be prompted to save the selection if so press the ENTER button to save the setting 7 Press the ESC button to cancel or return to previous LCD menu LCD SETTINGS CONFIGURATION There are 25 UPS settings that can be configured by the user 1 Press the ENTER button to activate the MAI...

Page 10: ...lish Español Spanish Français French Deutsch German English Generator Mode 2 Disable Enable Disable Communication Disable Enable Enable Dry Relay Set I P Power Fail Battery Low Summary Alarm UPS On Bypass UPS Fail I P Power Fail Converter Mode 3 Converter Off O P Freq 50Hz O P Freq 60Hz Converter OFF Screen Saver Disable 1 Minutes 5 Minutes 5 minutes Clear Event Log Activate None Button OFF LOCK D...

Page 11: ...attery Test portion of the LCD screen and the unit will perform a manual battery test GRAPHICAL LOAD BATTERY CAPACITY DISPLAY 1 Press the ESC button to return to UPS Status 2 Press the and buttons to scroll to the LOAD and BAT Capacity 3 Press the and buttons to scroll to the Charging or Discharging Capacity LOAD and BAT Capacity The LCD screen displays the Load and Battery capacity with a graphic...

Page 12: ...g the UPS from the wall receptacle before servicing the battery CAUTION Only use tools with insulated handles Do not lay tools or metal parts on top of the UPS or battery terminals Replacement Batteries Please refer to the front side of the UPS for the model number of the correct replacement batteries For battery procurement log onto www CPSww com or contact your local dealer Battery Disposal Batt...

Page 13: ...5 Load for 1 min 126 150 Load for 10 sec Battery Mode 105 130 Load for 10 sec 131 150 Load for 2 sec Short Circuit Protection UPS Output Cut off Immediately or Input Fuse Circuit Breaker Protection Battery Specifications 3 12V 7AH 3 12V 9AH 6 12V 7AH 6 12V 9AH Recharge Time Typically 5 hours Sealed Maintenance Free Yes Hot Swappable Yes Status Indicators LCD Screen Multi Function LCD Readout that ...

Page 14: ...s out of range Output Short Output short circuit Your attached equipment may have problems please remove them and check again Over Temperature High temperature sensor activates protection Check the fan for operation and if the ventilation hole has been covered Coldstart Lock UPS is locked to prevent consuming battery power during shipping Plug into utility power for first time operation Autorestar...