4.7 Connecting to Power Source

4.7.1 Installing the Power Cord 

1. Remove the 4 terminal strip cover screws 

(upper left hand corner)

2. Remove any convenient 3/4” knock-out of 

the UPS enclosure.

3. Install a Heyco Liquid Tight Cordgrip 
    (LTF-11) or equivalent, if not using conduit.
4. With the power cord disconnected from any 

supply source, route the power cord 
through the strain relief and attach it to the 
terminal strip.

5. Tighten the strain relief around the power 

cord to secure.

6. Re-install the terminal strip cover.
7. Plug-in the molded power plug on the front 

of the UPS control panel. 

Note: 

Be certain to utilize environmentally 

sealed strain-reliefs, cordgrips, or conduit at 
the AC Power entry point.

Note: 

Be sure to connect the power cord to 

each terminal (L/N/G) correctly and securely. 

Figure 14: AC Wiring (i)

Figure 15: AC Wiring (ii)

Remove 

terminal cover

Remove 

knock-out and 

add strain relief 

or conduit here

4.6 Battery Heater - BTH-150-8X (Optional)

Figure 12: Block Diagram of Battery Heater

Table 1: Battery Heater Specifications

Table 2: Block Diagram Descriptions

Figure 13: Battery Heater Dimensions

DESCRIPTION:

DIMENSIONS:

Input Voltage 

    (AC) 110V/60Hz

Wattage 

    120W

Line Cord Thermostat 

    OPEN

15˚C     CLOSE

5˚C

Thermal Fuse 

    84˚C

Mat Mounted Thermostat     OPEN

50˚C     CLOSE

35˚C

3

4

1

2

3

4

Heater

Location          Device 

                 Function

        Power Connector          AC Input

        Line Cord Thermostat     In low temperature conditions the thermostat    

 

                                                will allow power to flow to the heater mat coil

        Thermal Fuse 

        Final protection allows safe failure

        Mat Mounted                   The thermostat is to keep the temperature of

  

        Thermostat                   the battery heater within a pre-set range.

296

65

8

20

4

280

4-Ø10

28.55

115.5

37.55

28

16

Thermal Switch & Thermal Fuse
On Back

Heater Area

260

12

2-Ø4

Note:

 Make sure that the input voltage for the battery heater 

is 110V.  

Summary of Contents for CS150U48V3

Page 1: ...CS150U48V3 Installation Operation Manual K01 1504801 00...

Page 2: ...cting to Power Source 11 4 7 1 Installing the Power Cord 11 4 7 2 Outdoor Power Cord Selection 12 4 8 ONT Alarm Connections 13 5 Operation 13 5 1 Start Up 13 5 2 Controls and Operational LEDs 14 5 3 A...

Page 3: ...of 17 TABLE OF TABLES Table 1 Battery Heater Specifications 11 Table 2 Block Diagram Descriptions 11 Table 3 AC Line Cord 12 Table 4 Conduit Wires 12 Table 5 Controls and LED Indicators 14 Table 6 Ala...

Page 4: ...rify the supplied AC line voltage prior to installation using an AC voltage meter Verify branch circuit breaker or fuse on the service feed is correct for the equipment being installed Batteries may p...

Page 5: ...maintaining servicing or replacing batteries A battery showing signs of cracking leaking or swelling should be replaced immediately with a battery of identical type and rating The battery can energize...

Page 6: ...chnician for help CAUTION Any changes or modifications not expressly approved by Cyber Power could void the authority granted by the FCC to operate this equipment DO NOT USE FOR MEDICAL OR LIFE SUPPOR...

Page 7: ...r owners Page 6 of 17 Figure 1 Dimensions Front View Figure 2 Dimensions Side View 3 DIMENSIONS 17 14 inch 435 4 mm 7 09 inch 180 1 mm 5 79 inch 147 1 mm 15 75 inch 400 1 mm 16 inch 406 4 mm 15 30 inc...

Page 8: ...3 LED Indicators AC DC MODE BATTERY MISSING 1 BATTERY MISSING 2 DC OUTPUT 4 DC Output and Telemetry receptacles 5 Battery wiring harness plug in 6 Door clasp 7 Door padlock hasp 8 Door ground and bond...

Page 9: ...L Pole Mount Kit Pole Mount Bracket x 3 M8 Flange Nut x 6 M8 x 25L Hex Head Screws clamp center bracket to side brackets x 4 M8 Lock Washers x 4 M8 Flat Washers x 4 OPTIONAL Battery Heater Battery Hea...

Page 10: ...parately 3 Using the nuts included in the kit attach the left and right pole mount brackets to the threaded posts on the back side of the UPS enclosures as shown 4 Thread the 4 M8 x 25L hex head screw...

Page 11: ...tion is complete Wire Harness Vo Wire Strain Relief Wire Harness Vo Battery tray mounting hole Battery Harness Wire Plug in Battery Tray Mounting Screw 4 5 Installing the Battery Trays Battery Replace...

Page 12: ...nal L N G correctly and securely Figure 14 AC Wiring i Figure 15 AC Wiring ii Remove terminal cover Remove knock out and add strain relief or conduit here 4 6 Battery Heater BTH 150 8X Optional Figure...

Page 13: ...inner wire Use cord type with the suffix W W A or the words Water resistant or Outdoor marked on the flexible cord 15A 125V NEMA 5 15P or 15A 250V NEMA 6 15P SP 2 SPE 2 SPT 2 NISP 2 NISPE 2 NISPT 2 SP...

Page 14: ...Be certain to utilize environmentally sealed strain reliefs cordgrips or conduit at the cable exit point Note Output wires should be installed in accordance with Article 800 of ANSI NFPA 70 5 OPERATI...

Page 15: ...reset an output if it has been shut down due to an over current or short condition and the fault has been removed The cold start allows a start up of the system after a power outage and the batteries...

Page 16: ...nal in low state ON Batt signal in open state Low Batt signal in open state Missing Batt signal in open state Replace Batt signal in open state Description Condition normal AC input failure Battery is...

Page 17: ...factory orderable option Replaceable Yes Surge Protection and Filtering Lightning Surge Protection GR 1089 CORE Sect 4 Warning Diagnostics AC AC Battery Mode Indicator Output Output On Off Indicator...

Page 18: ...010 CyberPower Systems USA Inc All Trademarks are property of their owners Page 17 of 17 APPENDIX I Wall Mount Chart Recommended Screw Dimensions M8 x 25L or 3 8 x 1 L 7 09 inch 180 mm 16 inch 406 4 m...

Reviews: