Table 6: Alarms

5.3  Alarms

There are audible and visual alarm signals to alert the customer to abnormal and/or service 
affecting conditions present in the UPS.

Condition

Normal

On Battery

Low Battery

Battery 

Missing

Replace 

Battery

Status LED

AC/DC Mode 

LED is 

GREEN

AC/DC Mode 

LED is 

ORANGE

N/A

Missing 

Battery LED 

On

Missing 

Battery  LED 

On (RED)

Interface

“ON Batt” 

signal in low 

state

“ON Batt” 

signal in open 

state

“Low Batt” 

signal in open 

state

“Missing Batt” 
signal in open 

state

“Replace Batt” 

signal in open 

state

Description

Condition normal

AC input failure; Battery is 
supplying the power

When the battery is nearly 
depleted, the audible alarm 
will beep twice every one 
second.

The Missing Battery LED 
will be illuminated due to a 
missing battery.

The unit will perform a 
periodic battery test 
automatically without 
disrupting operation. If the 
battery needs to be 
replaced, the Missing 
Battery LED will be 
illuminated.

Alarm

No Audible 

Alarm

Beeps twice 

every 5 

seconds

Beeps twice 

every second

No Audible 

Alarm

No Audible 

Alarm

Summary of Contents for CS150U48V3

Page 1: ...CS150U48V3 Installation Operation Manual K01 1504801 00...

Page 2: ...cting to Power Source 11 4 7 1 Installing the Power Cord 11 4 7 2 Outdoor Power Cord Selection 12 4 8 ONT Alarm Connections 13 5 Operation 13 5 1 Start Up 13 5 2 Controls and Operational LEDs 14 5 3 A...

Page 3: ...of 17 TABLE OF TABLES Table 1 Battery Heater Specifications 11 Table 2 Block Diagram Descriptions 11 Table 3 AC Line Cord 12 Table 4 Conduit Wires 12 Table 5 Controls and LED Indicators 14 Table 6 Ala...

Page 4: ...rify the supplied AC line voltage prior to installation using an AC voltage meter Verify branch circuit breaker or fuse on the service feed is correct for the equipment being installed Batteries may p...

Page 5: ...maintaining servicing or replacing batteries A battery showing signs of cracking leaking or swelling should be replaced immediately with a battery of identical type and rating The battery can energize...

Page 6: ...chnician for help CAUTION Any changes or modifications not expressly approved by Cyber Power could void the authority granted by the FCC to operate this equipment DO NOT USE FOR MEDICAL OR LIFE SUPPOR...

Page 7: ...r owners Page 6 of 17 Figure 1 Dimensions Front View Figure 2 Dimensions Side View 3 DIMENSIONS 17 14 inch 435 4 mm 7 09 inch 180 1 mm 5 79 inch 147 1 mm 15 75 inch 400 1 mm 16 inch 406 4 mm 15 30 inc...

Page 8: ...3 LED Indicators AC DC MODE BATTERY MISSING 1 BATTERY MISSING 2 DC OUTPUT 4 DC Output and Telemetry receptacles 5 Battery wiring harness plug in 6 Door clasp 7 Door padlock hasp 8 Door ground and bond...

Page 9: ...L Pole Mount Kit Pole Mount Bracket x 3 M8 Flange Nut x 6 M8 x 25L Hex Head Screws clamp center bracket to side brackets x 4 M8 Lock Washers x 4 M8 Flat Washers x 4 OPTIONAL Battery Heater Battery Hea...

Page 10: ...parately 3 Using the nuts included in the kit attach the left and right pole mount brackets to the threaded posts on the back side of the UPS enclosures as shown 4 Thread the 4 M8 x 25L hex head screw...

Page 11: ...tion is complete Wire Harness Vo Wire Strain Relief Wire Harness Vo Battery tray mounting hole Battery Harness Wire Plug in Battery Tray Mounting Screw 4 5 Installing the Battery Trays Battery Replace...

Page 12: ...nal L N G correctly and securely Figure 14 AC Wiring i Figure 15 AC Wiring ii Remove terminal cover Remove knock out and add strain relief or conduit here 4 6 Battery Heater BTH 150 8X Optional Figure...

Page 13: ...inner wire Use cord type with the suffix W W A or the words Water resistant or Outdoor marked on the flexible cord 15A 125V NEMA 5 15P or 15A 250V NEMA 6 15P SP 2 SPE 2 SPT 2 NISP 2 NISPE 2 NISPT 2 SP...

Page 14: ...Be certain to utilize environmentally sealed strain reliefs cordgrips or conduit at the cable exit point Note Output wires should be installed in accordance with Article 800 of ANSI NFPA 70 5 OPERATI...

Page 15: ...reset an output if it has been shut down due to an over current or short condition and the fault has been removed The cold start allows a start up of the system after a power outage and the batteries...

Page 16: ...nal in low state ON Batt signal in open state Low Batt signal in open state Missing Batt signal in open state Replace Batt signal in open state Description Condition normal AC input failure Battery is...

Page 17: ...factory orderable option Replaceable Yes Surge Protection and Filtering Lightning Surge Protection GR 1089 CORE Sect 4 Warning Diagnostics AC AC Battery Mode Indicator Output Output On Off Indicator...

Page 18: ...010 CyberPower Systems USA Inc All Trademarks are property of their owners Page 17 of 17 APPENDIX I Wall Mount Chart Recommended Screw Dimensions M8 x 25L or 3 8 x 1 L 7 09 inch 180 mm 16 inch 406 4 m...

Reviews: