Function description

: The settings may be adjusted to the quality of the electricity in use. 

 

e. 

Slew  Rate:  Also  called  Dynamic  Frequency  Tolerance.  There  are  5  different  settings 
(0.25,0.5,1,2,4 Hz/Sec). The default value is 4Hz/sec. 

Function description

: “Slew Rate” indicates the tolerance of a device in accepting frequency 

variances. The lower “Slew Rate” results in less tolerance but better protection for the connected 
loads. 

 

f. 

Low Battery Shutdown Voltage: This function adjusts the EPS shutdown point according to the 
battery voltage. The default setting is 10V (with load). 
 

g. 

Mode Select: The standard mode (setting: 2) and the robust mode (setting: 1) are provided to 
select. Using the generators is suggested to select the robust mode (setting: 1), and using the 
computers is suggested to select the standard mode (setting: 2). 

 

The settable items are sorted by unit as in the following table

 

 

Step 3: 

Press and hold the toggle for 4 seconds. When the icons blink, the value of each item can be 

changed by slightly pressing the toggle. 

 

Step 4: 

To save the value and return to general mode, press and hold the toggle for 4 seconds. 

 

Note: If the machine is left idle for over 30 seconds during setup, it will turn off the backlight 

and return to general mode automatically.   

 

Note: If user wants to return to general mode without saving changes, there are two methods: 

1.  Wait for the backlight to turn off 

2.  Press and hold the “Display” toggle for 10 seconds 

 
 
 
 
 
 

 

 

Items 

Unit 

Icon Lit 

Delay Time 

Min 

ON BAT 

Charging Current 

ON BAT 

Nominal Output Voltage 

NORMAL MODE 

Static Frequency Tolerance 

NORMAL MODE 

Slew Rate 

None 

Low Battery Shutdown Voltage 

ON BAT 

Mode Select 

None 

None 

Summary of Contents for CPS600E

Page 1: ...0E CyberPower Europe CyberPower Systems B V Flight Forum 3545 5657DW Eindhoven The Netherlands Tel 31 0 40 2348170 Fax 31 0 40 2340314 Website http eu cyberpowersystems com E mail sales cyberpower eu...

Page 2: ...ACKING 4 AUTOMATIC VOLTAGE REGULATOR 4 HARDWARE INSTALLATION GUIDE 4 BASIC OPERATION 5 DESCRIPTION 5 REPLACING THE BATTERY 6 DEFINITIONS FOR ILLUMINATED LCD 7 EPS STATUS INQUIRY AND FUNCTIONS SETUP 8...

Page 3: ...he CE requirement CAUTION The building wiring socket outlet shockproof socket outlet must be easily accessible and close to the EPS CAUTION Please use only VDE tested CE marked mains cable e g the mai...

Page 4: ...EN 62040 2 Category C2 Radiated Emission IEC EN 62040 2 Category C2 Harmonic Current IEC EN61000 3 2 Voltage Fluctuations and Flicker IEC EN61000 3 3 EMS IEC EN61000 4 2 ESD IEC EN61000 4 3 RS IEC EN6...

Page 5: ...the EPS into a 2 pole 3 wire grounded receptacle wall outlet Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electrical demands e...

Page 6: ...Inquiry and Functions Setup section for more details 5 AC Outlet The unit has one Schuko type outlet for connected equipment to ensure temporary uninterrupted operation during a power failure Max Out...

Page 7: ...es regarding proper disposal of batteries Lead acid batteries should be recycled CAUTION Do not open or mutilate the batteries Released electrolyte is harmful to skin and eyes and may be toxic CAUTION...

Page 8: ...ays normal line mode AVR mode and battery backup mode 3 NORMAL MODE Icon This icon will illuminate when the EPS is working under normal conditions 4 ON BAT On Battery Icon When a severe brownout or bl...

Page 9: ...nctions User configurable functions are as follows a Delay Time The time delay between switching from Battery Mode to Line Mode There are 9 different settings The default setting is 0 minute Function...

Page 10: ...to select the robust mode setting 1 and using the computers is suggested to select the standard mode setting 2 The settable items are sorted by unit as in the following table Step 3 Press and hold th...

Page 11: ...y and the alarm reacts during the machine shut down LCD Warning Display Alarm Condition Solution Over Load Icon Constant tone Over Load Output Off Load exceed the rating of EPS Check total load to con...

Page 12: ...ct CyberPower Systems at service cyberpower eu com Batteries are discharged Recharge the unit for at least 4 hours Unit has been damaged by a surge or spike Contact CyberPower Systems about replacemen...

Page 13: ...0 230Vac On Battery Output Frequency 50 60 Hz 1 Overload Protection On Utility Fuse On Battery Internal Current Limiting Transfer Time 10 ms Typical Output Receptacles Schuko Type 1 External Battery V...

Page 14: ...CPS600E Copyright 2010 CyberPower Systems Inc 13...

Page 15: ...CPS600E Copyright 2010 CyberPower Systems Inc 14...

Page 16: ...Systems B V Flight Forum 3545 5657DW Eindhoven The Netherlands Tel 31 0 40 2348170 Fax 31 0 40 2340314 Website http eu cyberpowersystems com E mail sales cyberpower eu com Entire contents copyright 2...

Reviews: