27
TROUBLESHOOTING
EVENT
CODE
WARNING
ICON
POSSIBLE CAUSE
SOLUTION
N/A
Battery Mode
(Yellow)
UPS is operating
on battery power.
Save your data and perform
a controlled- shutdown.
01
Over Charge
(Red)
Battery is
overcharged.
Remove battery connector
and check charger voltage.
04
Battery Low
UPS is operating
on battery power
and the alarm
triggers when the
set percentage of
battery capacity
or remaining back-
up time is reached.
UPS will be
shutting down
soon due to
extremely low
battery voltage.
UPS will restart automatically
when acceptable utility
power returns.
05
Battery
Failure
UPS has failed in
Battery Test.
Check battery connector
and battery fuse.
Contact technical support
to replace the battery.
06
BAT
Disconnected
Missing battery
power.
Check battery connector
and battery fuse.
07
Service
Battery
The Battery
Replacement Date
has reached the
recommended 3
year maintenance
period.
If batteries have been
recently replaced, then reset
the Battery Replacement
Date using PowerPanel®
Business Edition-Agent
software, RMCARD interface
or through the LCD control
panel on the UPS (See LCD
Setting Configuration).
12
Load Over
XXX%
Your equipment
requires more
power than
the setting
in the Power
Management
Software (Power
Panel® Business)
will allow.
Shut off the non-essential
equipment or increase
the level in the Power
Management Software.
LCD will use FAULT ICON with RED to indicate the Fault or Warning status.