18
USING THE UPS SYSTEM
INDEX SET UP ITEMS
AVAILABLE SETTINGS
DEFAULT
SETTING
05
ECO Mode
[Disable] [Voltage= +/-15%] [Voltage = +/-10%]
When ECO mode is enabled the UPS will check the
following specifications of Bypass quality
(1) Bypass voltage is inside the [V Range= +/-10%]
(default setting) or [V Range= +/-15%].
(2) Bypass frequency is inside the +/-3Hz range of
output nominal frequency.
Disable
06
Manual Bypass
[Disable] [Enable]
When performing UPS maintenance, the user can
manually transfer the connected load to Bypass without
interrupting the output to the connected equipment.
Disable
07
Audible Alarms
[Disable] [Enable] [Only Bat Low]
User can [Disable] or [Enable] the buzzer sound.
Enable
08
EBM Number
[0] [1] [2] [3]
Sets the actual EBM (extended battery modules)
number to get the correct estimated runtime.
0
09
Generator Mode
[Disable] [Enable]
When the UPS input power source is a generator set
the UPS will operate normally without transferring
to Battery Mode when this is [Enable].
Disable
10
Communication
[Disable] [Enable]
All communication ports on the UPS are [Disable]
or [Enable]
Enable
11
Converter
Mode
[Disable][Output Freq = 50Hz] [Output Freq = 60Hz]
Sets [Output Freq = 50Hz] [Output Freq = 60Hz]
to convert the input frequency to required output
frequency.
Disable
12
Screen Saver
[Disable] [1 Minute] [5 Minutes]
Sets the amount of time the LCD screen stays on
after no user input. The [Disable] option keeps the
LCD screen on at all times.
5 Minutes
13
Clear Event Log
[Activate?]
Clears all the events stored in the LCD Control Panel
Event Log.
None
14
Signal Inputs
[Disable] [EPO] [ROO]
Sets [EPO] (Emergency Power Off) to shutdown
the UPS remotely when the contact is open.
Sets [ROO] (Remote On/Off) to turn On the UPS
remotely when the contact is close and turn Off the
UPS remotely when the contact is open. The On/Off
power button on front panel will be disabled when
set to [ROO].
Disable