Signal Silence
The operation of this button is similar to the Alarm Ack button except it will not scroll through multiple
priority acknowledged Alarms. Use the Alarm Ack button for this function. The Signal Silenced button
can be programmed to reset any active NAC circuits, Form C relays, Auxiliary output, Model RB 10-
40 relays and Model 301 Tandem Smoke Detector sounders. The Signals Silenced LED will turn on
and the message “Signals Silenced “will appear on the LCD when this button is pressed while an
alarm is present. Pressing this button will also send a record to the button press log.
The Signal
Silence button must be programmed to perform any of these functions. Follow local fire codes
and AHJ instruction when using this button.
Detector sounder silence
The operation of this button is similar to the Alarm Ack button except it will not scroll through multiple
priority acknowledged Alarms. Use the Alarm Ack button for this function. The intended use of this
button is to silence Model 301 tandem smoke detector sounders but the Detector sounder silence
button can also be programmed to reset any active NAC circuits and Model RB 10-40 relays. The
Signals Silenced LED will turn on and the message “Detector Sounders Silenced “will appear on the
LCD when this button is pressed while an alarm is present. Pressing this button will also send a
record to the button press log.
The Detector sounder silence button must be programmed to
perform any of these functions.
Follow local fire codes and AHJ instruction when using this
button.
Strobe Reset
The operation of this button is similar to the Alarm Ack button except it will not scroll through multiple
priority acknowledged Alarms. Use the Alarm Ack button for this function. The intended use of this
button is to reset NAC’s that are controlling strobes. This button can also be programmed to reset any
active NAC circuits and Model RB 10-40 relays. The Signals Silenced LED will turn on and the
message Strobes Reset “will appear on the LCD when this button is pressed while an alarm is
present. Pressing this button will also send a record to the button press log.
The Strobe Reset
button must be programmed to perform any of these functions.
Follow local fire codes and
AHJ instruction when using this button.
Reset
Pressing this button will reset the CP-3500D system to normal standby operation
. All active LED’s,
NAC circuits, Dry contact relays, Auxiliary output, RB 10-40 relays, LCD display and piezo will be
restored to normal standby condition. If the system is in test mode, pressing the reset button will take
the CP-3500D out of test mode. If any Alarm, Supervisory or Trouble that exists after reset will cause
the system to once again annunciate that condition.
Panel Test
Pressing this button while the CP-3500D is in normal standby will activate the Test LED. Refer to the
system testing section for additional information. Pressing reset will return the system to normal
standby.
Horns On
When pressed, this button will activate any NAC circuits and/or Model 301 sounders, turn the piezo
on steady
and the words “Alarm Circuits Activated will appear on the LCD screen. Pressing this
button will also send a record to the button press log.
The Horns On button must be programmed
to perform these functions. Refer to programming section for options.