P/N IM-C35KD Rev. C
2014 Commercial Wireless Systems International, LLC.
41
4.7.2 Programming the Sprinkler Supervisory Options
To activate or deactivate the Sprinkler Supervisory options, simply press ENTER to edit the field then
use UP/DOWN to make the desired selection. Choosing On activates the feature and Off deactivates
it. Press ENTER to exit edit mode and save the change. The first option if turned on will make alarms
from type C devices report as supervisory on the CP-3500D. The second option will make the
supervisory signals auto-restoring when the supervisory condition is cleared at the transmitter.
Turning on supervisory auto-restore will only have an effect on system operation if the first option
alarm C supervisory is also on.
The device type of the transmitter used for sprinkler supervisory should also be edited to as needed
to reflect the particular application such as water flow, tamper switch, PIV, OS&Y etc. Refer to section
4.4.5 to edit the device type. When an alarm occurs from a device programmed for sprinkler
supervisory, the word Alarm will be replaced by the word Supervisory. The screen will look similar to
the example shown below.
S u p e r v is o r y O p t i o n
Cancel
A l a r m C S u p e r v i s o r y : O f f
S u p e r v i s o r y A u t o - R e s t o r e : O f f
1 2 : 0 0 : 0 0 P M S u p e r v is o r y 0 1 / 0 1 / 0 9
S u p e r v i s o r y 0 4 8 1 1 d 1 1 : 5 9 : 0 0 P M 0 1 / 0 1 / 0 9
T a m p e r S w i t c h E a s t S t a i r w e l l