Page 25 of 58
•
IF THE TEST IS FAILED:
If it is not possible to maintain the pressure
at the required level the problem may be caused by blockages in the
pipework, incorrect pipe sizing or a faulty meter. If the problem is the
meter then TRANSCO, BORD GAIS or the propane supplier must be
called to adjust the governor. Do not use the appliance until the issue is
rectified.
•
IF THE TEST IS PASSED:
Disconnect the pressure gauge, replace the
pressure test point sealing screw and test the appliance for gas
soundness. Refit the front shelf.
Refit the Vanity/Shelf
The vanity/shelf is replaced by positioning it correctly where the “pips” on the
side locate on the notches on the side brackets.
Fit the Ceramics to the Fire
The fire can be supplied with an open ribbon flame or with ceramic fireplace
Logs or Pebbles. Only the ceramics that are supplied with the fire can be used.
The layout must be the same as detailed on the flowing pages. If the ribbon of
flame version is being installed go to page 30 to continue with the
commissioning.