Type of system

(select one) 

3 Phase/4 Wire

❏ 

1 Phase/3 Wire

3 Phase/3 Wire

❏ 

1 Phase/2 Wire

Phase Rotation

(if  Step 1 was 3 Phase, select one)

ABC Rotation

CBA Rotation

Choose Frequency

(select one)

❏ 

25Hz

50Hz

40Hz

60Hz

Incoming Line-to-Line Voltage

Enter from 100-600 Vac __ __ __

PT Primary Rating

(120 volt secondary)

Enter  from 120-500,000 volts
__ __ __ , __ __ __

CT Primary Rating

(5A secondary)

Enter from 5-10,000A

__ __ , __ __ __

GND CT Primary Rating

(5A secondary)

Enter from 5-10,000A

__ __ , __ __ __

Programming Options

(select one)

Faceplate Only

Input3 Key Only

Faceplate & IMPACC (recommended)

Input3 Key & IMPACC

Energy Resolution for Wh, varh, & VAh

(select one)

Kilowatt-hours

Megawatt-hours

Var Sign Convention

(select one)

Lagging vars & PF negative at load

Lagging vars & PF positive at load

Date and Time

Enter date and time if required
__________________

Change Password

Enter new 5 digit password if required
__ __ __ __ __ 

General Setup Settings Worksheet

13

Quick Start Procedure

(USER’S MANUAL SECTIONS 4-5)

During initial setup of your IQ Analyzer,
use Steps 1 - 5 below after the IQ Analyzer
has been mounted and wired using Sections
4-2 and 4-3, along with Figures 4-9 to 4-34 of
the User’s Manual as a reference. 

STEP #1:
Complete the General Setup Settings
Worksheet. This will require an understand-
ing of the electrical system configuration and
transformer ratios.

STEP #2:
Enter the Program Mode of the IQ Analyzer
If this is an initial startup, use factory default
passwords (10000 or 44444). 
(Program, F2, F4)

STEP #3: 
Enter General Setup Settings using the F1-F4
PBs from the information on page 13. (An
example is shown on the following pages.)

STEP #4:
Examine, understand and verify Metered
Values. Ensure display matches your system.

STEP #5: 
Troubleshoot problems.
Use the guide provided, the Help Mode
and/or the User’s Manual as a reference in
troubleshooting. 

Programming

Programming 

Summary of Contents for IQ Analyzer

Page 1: ...Cutler Hammer IQ Analyzer START QUICKSTART GUIDE...

Page 2: ...lly understand the wide array of features offered by your IQ Analyzer it is strongly recommended that operators read the User s Manual Following initial power up of the IQ Analyzer the displayed Meter...

Page 3: ...ol relaying analog inputs outputs and communications capabilities It will replace dozens of existing individual meters recorders and relays The IQ Analyzer displays a comprehensive list of metered par...

Page 4: ...nager PGM DISPMGR CUST 7 Display Mode USER S MANUAL SECTIONS 5 2 The IQ Analyzer monitors and displays a compre hensive list of metered parameters The Meter Menu provides easy access using Up Down PBs...

Page 5: ...and information Note on Sign Convention USER S MANUAL SECTIONS 5 22 As a factory default lagging vars and power factor are represented as negative values at the load This is a negative sign convention...

Page 6: ...ent damage The only exception is when connecting disconnecting ribbon cables at J2 or J3 11 Wiring installation for the IQ Analyzer must follow a suitable Wiring Plan Drawing and conform to applicable...

Page 7: ...___________ Change Password Enter new 5 digit password if required __ __ __ __ __ General Setup Settings Worksheet 13 Quick Start Procedure USER S MANUAL SECTIONS 4 5 During initial setup of your IQ A...

Page 8: ...SECTION 6 Meter a typical load on a 480 volt 3 phase 3 wire ABC phase rotation 60Hz system with 1200 5 CTs 50 5 ground CTs and no PTs Assume Kilowatt hour energy resolution and lagging vars Power Fac...

Page 9: ...Setup Blinking Type of System Blinking Month Blinking Parameter Digit Blinking Parameter Blinking Time Date Programming Example Password Programming Example From Main Menu Press and Release Program P...

Page 10: ...r Re enter program setpoints using proper password Customer established or factory default 44444 or 10000 1 I O Fuse Littlefuse Plug in Microfuse Catalog 273 250 0 25A 125V or equivalent Troubleshooti...

Page 11: ...Cutler Hammer For additional information or technical assistance contact ADVANCED PRODUCT SUPPORT CENTER 1 800 809 2772 www cutlerhammer eaton com...

Reviews: