background image

TROUBLE SHOOTING CONTINUED:

Replace thermostat if contacts are open when knob is fully
clockwise and water temperature is less than 190º F. You will
measure 120 volts (approximately) to ground from both thermo-
stat terminals when it is ON and from only one terminal when it
is OFF.

In this water boiler there are two elements in parallel. Failure of
either will cause very slow heating. Perform the following tests:

a. Clamp-on ammeter test: If both elements are good, you

will measure about 21 amps at 240 volts, 24 amps at
208 volts or 29 amps at 120 volts. If you measure only 10
to 12 amps, check the current to each element to identify
the defective part.

b . Ohmmeter or continuity test: Disconnect all power by

unplugging unit. Disconnect one terminal to measure each
element. They should each have continuity or measure
about 20 ohms.

2 . Defective thermo-

stat

3 . Burned out heat-

ing element

SOLUTION

POSSIBLE CAUSE

PROBLEM: 

WATER DOES NOT REACH PROPER TEMPERATURE

SOLUTION

POSSIBLE CAUSE

PROBLEM: 

 WATER OVERHEATS, ELEMENTS DO NOT SHUT OFF

Replace the thermostat. You can sometimes operate temporarily
by turning the thermostat knob to off until the boiling stops.

1 . Defective

thermostat

3

Summary of Contents for WB-10 -12

Page 1: ...WATER BOILER WB 10 12 6913 West Acco Street Montebello California 90640 Tel 800 421 6150 Technical Support Tel 800 995 0417 Fax 323 837 2401 Revised7 04...

Page 2: ...omes wired for 208 or 220 volt single phase 3 wire plus ground see wiring diagram 5 To connect the water boiler for 120 volt operation A The facility will have two wires one WHITE neutral and the othe...

Page 3: ...PROPER TEMPERATURE POSSIBLE CAUSE SOLUTION PROBLEM WATER WILL NOT REFILL 1 Water line closed or clogged filter 2 Valve coil burned out 3 Grounded probe 4 Defective water level control board TROUBLESH...

Page 4: ...ps at 240 volts 24 amps at 208 volts or 29 amps at 120 volts If you measure only 10 to 12 amps check the current to each element to identify the defective part b Ohmmeter or continuity test Disconnect...

Page 5: ...4 ILLUSTRATED PARTS LIST Water Boiler WB 10 12 B...

Page 6: ...PROBE WATER LEVEL SPACER 1 2 DIA ALUMINUM 8 32 TAP FITTING WATER INLET 1 4 FLARE TUBING ASSEMBLY 1 4 WATER INLET FITTING 1 4 x 3 8 FLARE BRASS ELBOW BUSHING 1 SNAP IN VALVE WATER INLET S 45 THERMOMETE...

Page 7: ...WATT 32 AMP 240 VOLT 8400 WATT 35 AMP L1 NEUTRAL L2 GROUND z 2 3 5 KW HEATING ELEMENTS INLET VALVE Rev 4 15 98 6 z z z z Water Boiler WB 10 12 120 VOLTS 2100 WATTS 17 5 AMPS 1 6 3 1 2 L PROBE ORANGE...

Page 8: ...ng and regular maintenance of this equipment 6 6 6 6 6 Dama Dama Dama Dama Damaged in transit ged in transit ged in transit ged in transit ged in transit Equipment damaged in transit is the responsibi...

Reviews: