3 Installation
3.1 Preliminary operations
Installation requirements:
»
Electrical Power Supply 120 V / 60 Hz grounded and with
protection devices. Ground fault receptacles are strongly rec-
ommended and may be required by local code.
»
Water supply connection
»
Water Drain connection
Th e installation must comply with local safety regula-
tions.
3.2 Positioning
Th e Mini NEB must be installed according to Pic. 3 in a
horizontal position with the air fi lter facing the ground,
with at least the minimal distance to allow proper air
fl ow and dispersion of humidity. Any other positioning or
shortened distances may compromise the performance of
the humidifi er.
3.2.1 Minimal distances
Pic. 3 - Positioning
A
B
C
D
Minimal (ft )
6.6
1.6
1.6
2.6
Suggested (ft )
9.8
3.3
4.9
4.9
Tab. 4 - Minimal distances
3.3 Electrical connections
3.3.1 Electrical wiring diagram
Pic. 4 - F3005 Wiring diagram
1
Humidifi er motor
4
External Humidistat Bridge
2
Floating switch
A
External Humidistat 120 V, 60 Hz, 0.2 A
(Not supplied)
3
Solenoid Valve
B
Line Protection (Not Supplied)
Tab. 5 - References
Th e control and safety devices, that are to be fi tted by the
installer, must include an adequate disconnecting switch
on both power supply lines.