background image

 

Manual No.  4801- 2997 Rev 1-15 

Secondary Sensing System 

26 of 42 

2.

 

Hang 

S

3

 with four screws. 

3.

 

Make sure all power supplies are disconnected before breaking any wires, or reaching into the 
system enclosure. 

4.

 

Open the 

S

3

 and find all connections.  Refer to wiring diagrams in 

Section 11 

of this manual. 

5.

 

Run temperature sensors out to locations inside the house.  Be sure that the sensors are in a safe 
location, free from any temperature influences (direct sunlight, water, etc.)  Use care when 
securing sensor wires so that the wire is not accidentally cut.  Any short, or break in the wire will 
cause improper sensor operation.  Next, run the wires into the enclosure via the watertight 
connector at the bottom of the box.  The wires should be cut off and stripped.  They next should 
be attached to the terminal block in the positions marked 

Sen 1, Sen 2 

and

 Sen 3

.  Note that the 

sensors are not polarity sensitive, and it therefore makes no difference as to which wire goes to 
which sensor terminal. 

6.

 

After the siren is mounted, it should be wired into the control box.  This is done at the terminal 
block locations labeled 

siren red

 and 

siren white

.  Note that polarity is important here and that the 

red siren wire must be connected into the 

siren red

 terminal block position and the same for the 

white wire.  Note also, any 12VDC device that uses less than 1.5 Amps of current could be 
connected in the siren’s place. 

7.

 

Connect wires from Alarm terminals to the alarm circuit or relay box.  (See wiring diagrams in 

Section 11.7 

for locations of terminals.) 

8.

 

If using a modem, connect wires from Modem terminals to the modem circuit or relay box.  (See 
wiring diagrams in 

Section 11.7 

for locations of terminals.) 

9.

 

If necessary, connect the 

S

3

 to the Cumberland Farm Manager Network. (See the connections in 

Section 11.10 

of this manual.) 

10.

 

Connect the AUX and CONTROL AUX connections.  Refer to 

Section 11.8 

diagram. 

11.

 

Remove jumpers for AUX & CONTROL connections if being used. 

12.

 

If connecting to an EV 3000/3001 controller, connect Local Net and Back-Up Network setting in 
Evolution controller (Plus models ONLY). 

13.

 

Wire Stage to Relay Card for Back-Up operation. 

14.

 

Set Stage Jumpers on Relay Cards in 

S

3

 or EV 3000/3001.  Refer to 

Section 11.6 

diagram. 

15.

 

Connect Vent/Tunnel Overrides. 

16.

 

Connect AC Power.  Refer to 

Section 11.3 

diagram. 

17.

 

Program the 

S

3

.  Refer to 

Section 5

9.3 

Sensor Recommendations 

It is important to note the Cumberland temperature sensors are fabricated using thermistors and are not 
interchangeable with sensors commonly used on controllers from other manufacturers.  The three temperature 
sensors may be installed in a variety of ways.  It is recommended that a sensor be located high enough from 
the floor so that livestock or poultry can not peck at it.  It is also essential that the sensor not be hung in front 
of heaters, fans or other devices that would cause false readings.  If a sensor is to be run from one building to 
another, it is recommended that the connection be made with underground-rated wire buried between the two 
structures.  This recommendation is to reduce the effects of lightning. 
 
Once again, the temperature sensors should be dropped as low in the house as possible while still being out 
of reach of the livestock or poultry.  And, as discussed earlier, it is recommended that the operator press the 
Test

 

button for ten to fifteen seconds at least twice a week to verify the operation of the alarm as well as to 

condition the livestock or poultry to the sound of the siren. 

Summary of Contents for Evolution S3

Page 1: ...01 2997 Rev 1 15 Owners Manual Secondary Sensing System CUMBERLAND Assumption IL 62510 Phone 217 226 4421 Fax 217 226 4420 Secondary Sensing System Owners Manual Cumberland 1004 E Illinois St Assumpti...

Page 2: ...m Mode 14 5 1 General Parameters 14 5 2 PC Compatible Cumberland Network Parameters 16 5 3 Alarm Function Parameters 16 5 4 Sensor Calibration Parameters 16 6 General Operation 17 6 1 Alarm Inputs 17...

Page 3: ...ernal Electrical Wiring 27 11 2 S3 Circuit Board Layout 28 11 3 Connecting AC Power to the S3 29 11 4 Connecting Sensors to the S3 30 11 5 S3 PowerTrak Override Settings and Wiring 31 11 6 S3 Relay Ca...

Page 4: ...the risk of overheating controller Warning Do not perform modifications or wiring with voltage applied Keep high voltage or AC separate from low voltage wires Warning When this controller is used in...

Page 5: ...s unit Therefore as with the Evolution Back Up System it is capable of driving up to 32 of the Evolution 3000 3001 relay outputs it can override the vent or tunnel inlets based on the level of Back Up...

Page 6: ...button is used to navigate thru settings and conditions When the Mode button is momentarily pressed the green LED Indicators changes to the next reading By pressing and holding the Mode button for at...

Page 7: ...ture Sensors 4 1 2 Target The Target mode displays the target temperature used for Zone Alarm Limits and Back Up Limits The Zone Alarm Limits and the Back Up Limits are referenced to the target much l...

Page 8: ...meter P2 See Section 5 4 1 4 Low Limit The Low Alarm Temperature is the low temperature at which the controller will indicate an alarm condition The Low Alarm Temperature is displayed and can be chang...

Page 9: ...ON as well as any alarm conditions which have occurred since the last reset The History Reset function is displayed after pressing the Mode Button once after the Low Temp is displayed The Zone 1 disp...

Page 10: ...lost AC power or the F1 fuse is blown Refer to Section 8 4 for fuse replacement information 4 2 3 Low Battery When the Low Battery RED LED indicator turns ON during loss of AC power the battery level...

Page 11: ...re highlights these indicators The CONTROL SYSTEM alarm can be enabled or disabled by using the circuit board jumpers Refer to the Circuit Board Layout in Section 11 2 If the jumper is installed the C...

Page 12: ...with Cool 1 Tunnel inlets operate with Cool 3 4 3 2 Ventilation Back Up Display and Selection Switch The Ventilation Back Up Display and Selection Switch are used to select and change the back up sett...

Page 13: ...t Acknowledge Alarm indicator This allows the user the ability to manually test his alarm siren and or alarm dialer As long as the button is depressed it will activate the alarm relay irregardless of...

Page 14: ...ameters by using the and buttons as needed When you have finished with the current setting press the Mode button to move to the next parameter 5 1 General Parameters General parameters are associated...

Page 15: ...his determines the number of seconds that the S3 will wait before turning Stages ON during power loss 10 to 60 seconds This feature is designed to help with generator start up P5 Fail Safe Vent Inlets...

Page 16: ...oring device and must be connected to Control Aux This setting changes the operation of the control system auxiliary alarm Contrary to its normal operation where an open signal would trigger an alarm...

Page 17: ...wer present at the electrical outlet and the Power Alarm is ON at the S3 the 3 Amp slow blow fuse located on the S3 circuit board Fuse F1 should be checked for a blown fuse To replace a fuse disconnec...

Page 18: ...6 2 2 Dry Contact N O and N C Contacts The S3 provides a set of dry contacts that can be used to trigger a modem auto dialer or other auxiliary equipment Both normally open N O and normally closed N...

Page 19: ...Operation the S3 always maintains the temperature between its high and low limits It accomplishes this by using its temperature sensors and its four stage outputs If the temperature drops below the Lo...

Page 20: ...the system still maintains the temperature as it does in Normal Operation In addition it receives commands from the master controller to turn on certain stages of heating or cooling There are many dif...

Page 21: ...aced based on the operation of stage equipment and should be the same as assigned in the EV 3000 Controller Jumpers are placed according the following table Type of Stage Operation Jumper Assignment C...

Page 22: ...ck Up Operation During Normal Operation the S3 always maintains the temperature between its high and low limits It accomplishes this by using its temperature sensors and its four stage outputs If the...

Page 23: ...u do not assign a relay output to Cool1 you will not have back up protection for minimum ventilation It is also important to choose the correct fans to back up For example choose a fan that is not you...

Page 24: ...the power has been out for more than one minute The other situation could be caused by the 120VAC 3 amp fuse blown If the Power Out alarm condition is active and you find that there is power present a...

Page 25: ...accurate Place this thermometer next to the temperature sensor for at least 10 minutes Insure that there are no strong breezes or winds blowing on the thermometer and the sensor being calibrated Note...

Page 26: ...ms in Section 11 7 for locations of terminals 9 If necessary connect the S3 to the Cumberland Farm Manager Network See the connections in Section 11 10 of this manual 10 Connect the AUX and CONTROL AU...

Page 27: ...at least once per quarter You will need to have two people one at the sensor with a trusted thermometer and one at the controller to calibrate the sensor 11 Wiring Diagrams Schematics etc The followin...

Page 28: ...Manual No 4801 2997 Rev 1 15 Secondary Sensing System 28 of 42 11 2 S3 Circuit Board Layout...

Page 29: ...Manual No 4801 2997 Rev 1 15 Secondary Sensing System 29 of 42 11 3 Connecting AC Power to the S3 Secondary Sensing System Inset A Inset A...

Page 30: ...g System 30 of 42 11 4 Connecting Sensors to the S3 White Shield Sen 3 Black Black Sen 2 White Shield White Shield Sen 1 Black Inset A SENSOR SENSOR SENSOR White Shield White Shield White Shield Black...

Page 31: ...DE Vent Override Cool 1 Tunnel Override Cool 3 Vents Tunnel Will Wire The Same NOTE If curtain is setup to pull curtain up to open then reverse wires connected to Open and Close terminals Inset B Tunn...

Page 32: ...inals NOTE Ensure the Relay Card connector and the PCB header are properly aligned during stand off and Relay Card installation NOTE The Relay Card is necessary on Stand Alone systems ONLY If S3 is us...

Page 33: ...ng System 33 of 42 11 7 Connecting an Alarm or Siren to the S3 Inset A White Red NO NC Com Alarm Out Siren Internal Switch Non alarm position Connect to alarm modem auto dialer etc as desired White Re...

Page 34: ...ev 1 15 Secondary Sensing System 34 of 42 11 8 Connecting Auxiliary Inputs to the S3 Inset B Inset A NOTE The jumper across J6 J8 and or J10 must be removed if an external alarm input is connected Sec...

Page 35: ...ry alarm outputs to the S3 auxiliary inputs The alarm activates when the connection is broken between the OUT and IN terminals NOTE 1 As long as a path for current flow is present the Secondary Sensin...

Page 36: ...1 10 Connecting Local Network Connections to the S3 Warning Tape Shield To Prevent Damage NOTE Harness to connect Local Network and Secondary Sensing system together are connected included in the Seco...

Page 37: ...Manual No 4801 2997 Rev 1 15 Secondary Sensing System 37 of 42 11 11 Connecting the S3 to the HH Net Inset B Inset A Secondary Sensing System...

Page 38: ...rminal Block 4 pos 3006 5079 CONN Terminal Block 5 pos 3006 5092 CONN Terminal Block 6 pos 3540 0149 DIGITAL_IC LTC1483CN8 Network Chips 3010 2991 FUSE 3 AMP 5mmX20mm slowblow F1 F2 3701 6066 PIC S3 P...

Page 39: ...413 42 4 5 8 12 493 68 20 6 836 93 33 9 24 055 43 6 1 12 325 68 5 20 3 6 779 93 4 34 1 23 82 43 3 6 3 12 215 68 9 20 5 6 695 93 9 34 4 23 472 43 9 6 6 12 051 69 4 20 8 6 612 94 5 34 7 23 13 44 4 6 9...

Page 40: ...3 Error Code Description Explanation LnE Local Network Error The Back Up has lost Communications with the Master Controller NOTE During this condition the Back Up will run Cool 1 on a 5 minute timer L...

Page 41: ...nditions and Limitations THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE LIMITED WARRANTY DESCRIPTION SET FORTH ABOVE SPECIFICALLY GSI MAKES NO FURTHER WARRANTY OF ANY KIND EXPRESS OR IMPLIED INCLUDING...

Page 42: ...Manual No 4801 2997 Rev 1 15 Secondary Sensing System 42 of 42...

Reviews: