Welcome To Your New World of Better Living with Culligan Water.

Congratulations on selecting the Aquasential Non-Backwashing System� With Culligan’s many years of knowledge and 

experience in water treatment, you can be confident that the model you selected has been designed and engineered to 

provide years of service with a minimum of care and attention�
If this is your first experience having filtered, conditioned water in your home, you’ll love the amazing difference it makes� 

We promise that you’ll never want to be without it again�
The Culligan® Aquasential Non-Backwashing System is designed to meet the needs of applications for high quality water� 

This manual contains important information about the unit, including information needed for installation, operating, and 

maintenance procedures� A troubleshooting section provides a guide for quick and accurate problem solving�
This manual is based on information available at the time it was finalized, approved, and published� Continuing design 

refinement could cause changes that may not be included in this publication�
Your local independently operated Culligan dealer employs trained service and maintenance personnel who are 

experienced in the installation, function and repair of Culligan equipment� This publication is written specifically for 

these individuals and is intended for their use�

NOTE! 

This Owners Guide is also available to you online. 

www.culligan.com/support/product-information/product-manuals

Culligan Aquasential Non-Backwashing Systems have been tested and certified 

by WQA against NSF/ANSI 372 for Lead Free Compliance and to CSA B483.1 for 

material safety and structural integrity.

Downflow-Fiberglass 8x44˝ Empty, Downflow-Fiberglass 9x48˝ Empty, Downflow-

Fiberglass 9x48˝ Empty, Downflow-Fiberglass 10x54˝ Empty, Downflow-Fiberglass 

12x52˝ Empty. Downflow-Quadra-Hull 9x48˝ Empty, Downflow-Quadra-Hull 10x54˝ 

Empty, Downflow-Quadra-Hull 12x52˝ Empty, Downflow-Quadra-Hull 14x65˝ Empty, 

Downflow-Quadra-Hull  16x65˝  Empty,  Upflow-Fiberglass  8x44˝  Empty,  Upflow-

Fiberglass  9x48˝  Empty,  Upflow-Fiberglass  10x54˝  Empty,  Upflow-Quadra-Hull 

9x48˝ Empty, Upflow-Quadra-Hull 10x54˝ Empty are certified by WQA to NSF/ANSI 

372 for Lead free compliance and to CSA B483.1 for material safety and structural 

integrity. Not certified for contaminant reductions. 

Downflow-Fiberglass 8x44˝ Cullar D+, 1 CF; Downflow-Fiberglass 9x48˝ Cullar D+, 1 CF; Downflow-Fiberglass 

9x48˝ Cullar D+, 1.5 CF; Downflow-Fiberglass 10x54˝ Cullar D+, 1.5 CF; Downflow-Fiberglass 10x54˝ Cullar 

D+, 1.5 CF; Downflow-Fiberglass 10x54˝ Cullar D+, 2.0 CF; Downflow-Fiberglass 12x52˝ Cullar D+, 2.75 CF; 

Downflow-Quadra-Hull  9x48˝  Cullar  D+,  1  CF;  Downflow-Quadra-Hull  9x48˝  Cullar  D+,  1.5  CF;Downflow-

QuadraHull  10x54˝  Cullar  D+,  1.5  CF;  Downflow-Quadra-Hull  10x54˝  Cullar  D+,  2.0  CF;  Downflow-Quadra-

Hull 12x52˝ Cullar D+, 2.75 CF; Downflow-Quadra-Hull 14x65˝ Cullar D+, 4.5 CF; and Downflow-Quadra-Hull 

16x65˝ Cullar D+, 6 CF are certified by WQA to NSF/ANSI 372 for Lead free compliance and to CSA B483.1 for 

material safety and structural integrity. Not certified for contaminant reductions. System must use Culligan 

Cullar D+ media only otherwise WQA certification will be void. 
Downflow-Fiberglass 8x44˝ Cullar S, 1 CF; Downflow-Fiberglass 9x48˝ Cullar S, 1.5 CF; Downflow-Fiberglass 

10x54˝  Cullar  S,  2  CF;  Downflow-Fiberglass  12x52˝  Cullar  S,  2.75  CF;  Downflow-QuadraHull  9x48˝  Cullar 

S,  1.5  CF;  Downflow-Quadra-Hull  10x54˝  Cullar  S,  2  CF;  Downflow-Quadra-Hull  12x52˝  Cullar  S,  2.75  CF; 

Downflow-Quadra-Hull 14x65˝ Cullar S, 4.5 CF and Downflow-Quadra-Hull 16x65˝ Cullar S, 6 CF are certified 

by WQA to NSF/ANSI 372 for Lead free compliance and to CSA B483.1 for material safety and structural 

integrity. Not certified for contaminant reductions. System must use Culligan Cullar S media only otherwise 

WQA certification will be void. 

Thank You!

Summary of Contents for Aquasential 2021

Page 1: ...Aquasential Non Backwashing Systems Models from 2021 DCO 200276 02 02 21 CAT 01037452 Rev C 2021 Culligan International Company ...

Page 2: ... Analytical Laboratory is certified to perform coliform and E coli testing We strive to provide our customers with the testing they need at the lowest possible cost with the quickest turn around time STANDARD WATER TESTING For sizing systems and general chemical water characteristics WELL WATER TESTING Basic Realtor Drilling Surveilance Expanded Gold SPECIAL WATER TESTING Hemodialysis Scale Resin ...

Page 3: ...igan Customer 5 Thank You 6 Specifications 8 Application Operation 10 When How to Bypass Your System 11 Things to Check Before You Call For Service 12 Care and Cleaning of Your Water System 13 Records Data 14 Culligan Limited Warranty 15 Table of Contents ...

Page 4: ...E Note is used to emphasize installation operation or maintenance information which is important but does not present any hazard Caution CAUTION Caution is used when failure to follow directions could result in damage to equipment or property Warning WARNING Warning is used to indicate a hazard which could cause injury or death if ignored The CAUTION and WARNING paragraphs are not meant to cover a...

Page 5: ...ision or instruction Children should be instructed not to play with this appliance NOTE This system is not intended for use with water that is microbiologically unsafe or of unknown quality without adequate disinfection either before or after the system Check with your public works department for applicable local plumbing and sanitation codes Follow local codes if they differ from the standards us...

Page 6: ...ty Downflow Fiberglass 12x52 Empty Downflow Quadra Hull 9x48 Empty Downflow Quadra Hull 10x54 Empty Downflow Quadra Hull 12x52 Empty Downflow Quadra Hull 14x65 Empty Downflow Quadra Hull 16x65 Empty Upflow Fiberglass 8x44 Empty Upflow Fiberglass 9x48 Empty Upflow Fiberglass 10x54 Empty Upflow Quadra Hull 9x48 Empty Upflow Quadra Hull 10x54 Empty are certified by WQA to NSF ANSI 372 for Lead free c...

Page 7: ... to NSF ANSI 372 for Lead free compliance and to CSA B483 1 for material safety and structural integrity Not certified for contaminant reductions System must use Culligan Cullneu media only otherwise WQA certification will be void Products manufactured and marketed by Culligan International Company Culligan and its affiliates are protected by patents issued or pending in the United States and othe...

Page 8: ...8x44 1 1 33 49 5 10 1 10 5 6 3 75 01039896 Downflow Fiberglass 9x48 1 1 87 53 5 11 11 3 12 3 75 01039897 Downflow Fiberglass 9x48 1 5 1 87 53 5 11 11 3 12 5 5 01039898 Downflow Fiberglass 10x54 1 5 2 59 60 12 3 12 3 15 5 5 01039899 Downflow Fiberglass 10x54 2 0 2 59 60 12 3 12 3 15 7 5 01039900 Downflow Fiberglass 12x52 2 75 3 60 58 14 14 20 10 01039901 Downflow Quadra Hull 9x48 1 0 1 87 53 5 11 5...

Page 9: ...00 2 59 60 12 3 12 3 7 01039928 Upflow Quadra Hull 9x48 75 1 87 53 5 11 5 11 8 5 01039929 Upflow Quadra Hull 10x54 100 2 59 60 12 8 12 8 7 Empty DF Systems Media not included Downflow System System Part Number Tank Type Tank Size in Recommended Maximum Media loading Tank Volume ft Height in Width in Length in 01039930 Downflow Fiberglass 8x44 1 0 1 33 49 5 10 1 10 5 01039931 Downflow Fiberglass 9x...

Page 10: ...ntial and light commercial applications Aquasential Non Backwashing systems are available in four sizes with Culligan fiberglass tanks and five sizes of Culligan Quadra Hull tanks Complete systems include the Culligan In Out Head the filter tank with manifold bypass valve tank adapter and miscellaneous parts to complete the system Systems supplied with media include the proper amount of media and ...

Page 11: ...ligan water filter is a Cul Flo Valv Bypass valve To bypass the unit turn the blue knob clockwise To return to filtered water service turn the blue knob counter clockwise Figure 1 Bypass Position About 3 8 Bypassed To BYPASS turn the blue knob clockwise see directional arrow on end of knob until the knob stops as shown in Figure 1 DO NOT OVERTIGHTEN Figure 2 Service Position About 1 1 4 A screwdri...

Page 12: ...ur water supply is work ing Open a tap ahead of the filter outside tap to see if you have any water pressure If you have water pressure check the bypass valve If it is in the Service position put it into the bypass and call your Culligan dealer for service If You Have A Cartridge Filter Installed If your system has a cartridge type filter installed prior to the Aquasential Non Backwashing System m...

Page 13: ...nt Culligan water systems are sold for use with potable water only If at any time the water becomes contaminated such as during a boil water situation the operation of the water system should be discontinued until it is verified that the water is again potable To do this turn the knob on the bypass valve to the bypass position Then call your Culligan dealer to have your system sanitized before it ...

Page 14: ... month _________ Recommended Dealer Service _____ Test Water _____ Evaluate Condition of Filter Media _____ Replace or Add Filter Media as Necessary Water Analysis Hardness _____________________ grains gallon Total Dissolved Solids TDS ___________________ mg l pH level acidity ______________________ S U Alkalinity_______________________________grains gallon Chloride ____________________________ mg...

Page 15: ... all implied warranties including without limitation warranties of merchantability and fitness for particular purpose to the extent required by law any such implied warranties are limited in duration to the one year period specified above for the entire filter As a manufacturer we do not know the characteristics of your water supply or the purpose for which you are purchasing a water filter The qu...