21
The installation must be carried out by a suitably
qualified person, in accordance with the current
version of the following.
o
UK Regulations and Safety Standards or their European
Norm Replacements.
o
Building Regulations (issued by the Department of the
Environment).
o
Building Standards (issued by the Scottish Development
Department).
o
IEE Wiring Regulations.
o
Electricity At Work Regulations.
Positioning
The adjacent furniture must be able to withstand a
minimum temperature rise of 85°C above the
ambient temperature of the room it is located in,
during periods of use.
This appliance is classified as Class 3 and therefore is to be built into
a kitchen unit (depending on size) or 600 mm worktop that is at
least 30 mm thick. The following minimum clearance distances must
be observed:-
o
700 mm between the hob surface and the underside of any
horizontal surface above it.
o
50 mm clearance around the front, back and sides of the
appliance, measured from the cut out.
o
If the hob is positioned so that the right or left hand side of the
appliance will be near to the edge of a kitchen unit. There must
be a gap of at least 150 mm between the side of the hob and
the vertical surface of the kitchen unit.
Installation
Summary of Contents for UBTCC75
Page 1: ...User Manual UBTCC75 Built in ceramic hob ...
Page 28: ...28 ...