![CTC Union EcoPart 425-435 Installation And Maintenance Manual Download Page 15](http://html1.mh-extra.com/html/ctc-union/ecopart-425-435/ecopart-425-435_installation-and-maintenance-manual_2693353015.webp)
15
CTC EcoPart i425-i435 Pro
General Information
1
3
2
4
5
8
6
7
9
10
11
12
13
15
14
16
17
1. Brine (heat source)
2. Water
3. Evaporator
4. Condenser
5. Compressor
6. Expansion valve (electronic)
7. Drying filter
8. Refrigerant exchanger
9. Low pressure sensor
10. High pressure sensor
11. High pressure switch
12. Temperature suction gas
13. Temperature hot gas discharge
14. Temperature brine
15. Temperature water out
16. Temperature water in
17. Control expansion valve
2.5 Refrigerant system
The schematic diagram shows the refrigerant system for each integrated
heat pump module.
2.6 Operating range
CTC EcoPart’s pressure-controlled operations monitoring means that the
brine temperature (B) and heat medium temperature (H) can automatically be
increased where this is possible.
Operating condition:
B temp/H temp °C
1
-5 / 25
2
20 / 25
3
-5 / 61
4
20 / 64
Operating limits as per the table above are defined in accordance with EN 14511-4.