Form I-RA/D 350/500, Page 8
Heater
Placement
Do not attempt to install this heater until you have read and under
-
stand this manual!
Placement is critical to the efficient operation of this heater.
Locate a specific central area for placement of your heater.
Measure all distances to comply with the specific code requirements and
minimum clearances listed below.
Refer to the section on Venting your heater for vent requirements and
recommendations.
Locate the heater so that suitable means shall be provided to facilitate
regular cleaning and maintenance of the heater (i.e. permanent platform,
portable stairs, ladder, etc.).
WARNING: You must comply with all requirements on
distance from heater to combustibles.
In Canada, for additional information on installation clearances, refer
to CAN/CSA-B139-M91, “Installation Code for Oil Burning Equipment,”
Clause 7.0 - Installation Clearances.
WARNING: Clearances apply to all combustibles. Do
not leave paper, rags, or any moveable combustibles
near the heater or store gasoline or any other
flammable fluid near this appliance.
Fan Models
Blower Models
RA350/500
RAD350/500
inches
mm
inches
mm
Top
6
152
6
152
Front
48
1219
48
1219
Side (Burner)*
18
457
18
457
Side (Opposite
Burner)*
18
457
18
457
Rear*
24
610
6
152
Bottom
18
457
18
457
Flue Pipe
18
457
18
457
*Allow for service access.
Minimum
Clearances
from
Combustibles
Summary of Contents for RA 350