TABLE 9.6: PIPE AND CIRCULATOR SIZING FOR INDIRECT WATER HEATER LOOP
BOILER
MODEL
(a)
(b)
(c)
(d)
(e)
(f)
PIPE
SIZE
FLOW
MAX. I.W.H.
PRESSURE
DROP
CROWN INDI-
RECT WATER
HEATERS
CIRCULATOR
MODEL
I.W.H. LOOP MAX
EQUIVALENT
LENGTH
(in NPT)
(GPM)
(ft HEAD)
(ft)
BWC070
1
6.0
1.7
MS-26 (*)
MS-40 (*)
MSH-40H (*)
MT040GBR (*)
Taco 008
122
BWC090
1
8.0
3.0
MS-26
MS-40 (*)
MSH-40H
MT040GBR (*)
Taco 0014
78
BWC120
1
8.0
3.0
MS-26
MS-40
MSH-40H
MT040GBR
MT050GBR
MT065GBR
MT080GBR
Taco 0014
108
BWC120
1
8.0
5.0
MSH-53H
Taco 0014
70
BWC151
1
8.0
3.0
MS-26
MS-40
MSH-40H
MT040GBR
MT050GBR
MT065GBR
MT080GBR
Taco 008
49
BWC151
1
8.0
5.0
MS-53
MS-53H
MSH-79(*)
Taco 0014
150
TABLE 9.6 NOTES:
1) Indirect water heaters with an asterisk (*) will not achieve their catalog rating due to inadequate boiler water flow
and/or inadequate boiler output.
48
TABLE 9.7: FITTING EQUIVALENT LENGTHS
FITTING
PIPE SIZE
EQUIVALENT LENGTH (ft)
90 ELBOW
1
2.75
TURN IN TEE
1
5.50
RUN OF TEE
1
1.75
SWING CHECK
1
7.00
GATE VALVE
1
0.60
Summary of Contents for BIMINI BUDDY BWC090
Page 2: ......
Page 9: ...7 Figure 5 1 Wall Mounting Hole Locations ...
Page 10: ...Figure 5 2 Boiler Mounting Hardware 8 ...
Page 43: ...FIGURE 7 51 CONDENSATE PIPING ARRANGEMENT 41 ...
Page 56: ...54 Figure 10 1 Wiring Connections Diagram ...
Page 57: ...55 Figure 10 2 Ladder Diagram ...
Page 58: ...56 Figure 10 3 Wiring of Isolation Relay for Control of Two Heating Circulators ...
Page 76: ...74 ...
Page 79: ...77 ...
Page 80: ...78 ...
Page 81: ...79 ...
Page 82: ...80 ...
Page 84: ...82 150 151 152 153 154 155 ...
Page 85: ...83 156 157 158 159 160 161 ...
Page 86: ...162 84 ...