47
TABLE 9.5: PIPE AND CIRCULATOR SIZING FOR BOILER LOOP
BOILER
MODEL
(a)
(b)
(c)
(d)
(e)
PIPE
SIZE
FLOW
TEMP
RISE
CIRCULATOR
MODEL
BOILER LOOP
MAX EQUIVALENT
LENGTH
(in NPT)
(GPM)
(F)
(ft)
BWC070
1
6.0
21
Taco 007
67
BWC070
1
6.0
21
Taco 008
171
BWC090
1
8.0
21
Taco 0014
135
BWC120
1
8.0
29
Taco 0014
166
BWC120
1
9.0
25
Taco 0014
95
BWC120
1
12.0
19
Taco 0013 (Note #1)
51
BWC151
1
8.0
34
Taco 008
106
BWC151
1
11.0
25
Taco 0014
68
BWC151
1
14.0
19
Taco 0013 (Note #1)
59
NOTE: 1) Use isolation relay between Taco 0013 and BWC - see Figure 10.3