3) Two basic types of errors codes are shown on the display:
• Soft Lockout Codes – When a soft lockout occurs, the boiler will shut down and the display will alter-
nate between the number “9” and the letter “b” followed by a two digit service code. A list of these
codes, and their meanings, is shown in Table 14.3. The boiler will automatically restart once the condi-
tion that caused the lockout is corrected.
• Hard Lockout Codes – When a hard lockout occurs, the boiler will shut down and the display will
flash the letter “E” followed by a two digit service code. A list of these codes, and their meanings, is
shown in Table 14.4. Once the condition that caused the lockout is corrected, the boiler will need to be
manually reset using the RESET button on the display.
4) If an outdoor sensor is installed, the boiler will automatically adjust the heating zone set point temperature
based on the outdoor reset curve in Figure 12.4. The maximum set point is defined by parameter 4 (factory set
to 180°F) when the outdoor temperature is 0°F or below. The minimum set point temperature shown is 130°F
when the outdoor temperature is 60°F or above. As the outdoor temperature falls, the supply water target
temperature increases. For example, if the outdoor air temperature is 30°F, the set point temperature for the
supply water is 155°F.
5) An indirect water heater thermostat can be connected between terminals 7 and 8 on the terminal strip. When
this thermostat closes, the central heating circulator will be turned off and the DHW circulator will be turned
on.
6) An external limit control can be installed between terminals 3 and 4 on the terminal strip. Be sure to remove
the jumper between terminals 3 and 4 when adding an external limit control to the system. If the external limit
opens, the boiler will shut down and error code “b 26” will be displayed. If the limit installed is a manual
reset type, it will need to be reset before the boiler will operate.
Table 12.3: Boiler Status
First Digit
Boiler Status
0
Burner off - No call for heat or DHW
1
Pre-purge or post-purge
2
Ignition
3
Burner responding to call for heat
4
Burner responding to call for DHW
5
Checking air pressure switch
6
Burner off - Set point temperature has been reached
7
Call for heat ended. 10s heating post pump period
8
Call for DHW ended. 10s DHW post pump period
9 and b
Flashing
Burner off - on soft lockout. See Troubleshooting
Section to determine meaning of error code.
A
Boiler responding to call from heating zone
H
Burner on - Held in high fire
L
Burner on - Held in low fire
Summary of Contents for BIMINI BUDDY BWC090
Page 2: ......
Page 9: ...7 Figure 5 1 Wall Mounting Hole Locations ...
Page 10: ...Figure 5 2 Boiler Mounting Hardware 8 ...
Page 43: ...FIGURE 7 51 CONDENSATE PIPING ARRANGEMENT 41 ...
Page 56: ...54 Figure 10 1 Wiring Connections Diagram ...
Page 57: ...55 Figure 10 2 Ladder Diagram ...
Page 58: ...56 Figure 10 3 Wiring of Isolation Relay for Control of Two Heating Circulators ...
Page 76: ...74 ...
Page 79: ...77 ...
Page 80: ...78 ...
Page 81: ...79 ...
Page 82: ...80 ...
Page 84: ...82 150 151 152 153 154 155 ...
Page 85: ...83 156 157 158 159 160 161 ...
Page 86: ...162 84 ...