Overload Indicator Light (Red)

The overload indicator light 

comes on when an overload of 

a connected electrical device 

is detected, the inverter 

control unit overheats, or the 

AC output voltage rises. Then, 

the AC protector will trip, 

stopping power generation in 

order to protect the generator and any connected electric 

devices. The AC pilot light (Green) will go off and the overload 

indicator light (Red) will stay on, but the engine will not stop 

running.
When the overload indicator light comes on and power 

generation stops, proceed as follows:
1.  Turn off any connected electric devices and stop the 

engine.

2.  Reduce the total wattage of connected electric devices 

within the rated output.

3.  Check for blockages in the cooling air Inlet and around the 

control unit. If any blockages are found remove.

4.  After checking, restart the engine.

NOTE

:  The overload indicator light may come on for a few 

seconds at first when using electric devices that require 

a large starting current, such as an air conditioner  or a 

water pump. However, this is not a malfunction.

AC Pilot Light (Green)

The AC pilot light comes on 

when the engine starts and 

produces power.

Ground (Earth) Terminal

The ground terminal on this 

generator is connected to NON-

current carrying parts of the 

generator frame and to each AC 

outlet. Before attaching a 

ground (earth) lead, consult with 

a qualified electrician on the 

intended use of this generator.

AC Circuit Breaker

The AC Circuit Breaker will trip 

to protect the electric device 

when current is too heavy.

Folding Handle

This generator is fitted 

with a folding handle 

set to enable the user 

to manoeuvre the 

generator with ease. To 

engage, lift handle up 

and lock handle in 

place. To fold down, press down on both locking levers at the 

same time and the handle will fold down. Do not use 

generator with handle set in the fixed position. Do not use the 

handle set to raise the generator off the ground.

Maintenance Door

Make sure that the maintenance door is closed while the 

engine is running. Open and close maintenance doors for unit 

maintenance.

In the case of no electrical start, 

open the right maintenance 

door and start the engine by 

recoil starter.

Right door: 

Inspection/

replacement of engine oil; 

manual start.

Left door: 

Inspection/

replacement of spark plugs; 

inspection/cleaning of air filter; 

drain of carburetor.
Open maintenance 

door: Rotate lock 90° 

counterclockwise.
Close maintenance door: 

Rotate lock 90° clockwise.

Summary of Contents for Cromtech 7000ie

Page 1: ...CROMTECH 7000ie OPERATION MANUAL INVERTER GENERATOR...

Page 2: ...claim under the warranty you must return the product with proof of purchase to the closest warranty agent or to the place of purchase Where a failure does not amount to a major failure Crommelins Mac...

Page 3: ...lert Symbol including DANGER You WILL be KILLED or SERIOUSLY HURT if you don t follow instructions WARNING You CAN be KILLED or SERIOUSLY HURT if you don t follow instructions CAUTION You CAN be HURT...

Page 4: ...ation Do not place flammable objects close to the exhaust when generator is operating Keep at least one metre away from flammable materials Do not use in confined spaces WARNING Do not connect to a ho...

Page 5: ...t see or smell PETROL AND ITS VAPOUR ARE FLAMMABLE AND EXPLOSIVE Keep away from heat sparks ame sources DO NOT refuel when operating GENERATORS PRODUCE ELECTRICITY THAT CAN CAUSE SERIOUS INJURY OR DEA...

Page 6: ...or 17 Air filter 18 Frame shock absorber bracket left 19 Left maintenance door 20 Spark plug 21 Combination switch 22 Tank cover front Control Panel Diagram 1 2 3 4 5 6 9 10 11 12 7 8 INVERTER GENERAT...

Page 7: ...t Button to start the engine Recoil Starter When battery voltage is too low or flat use the manual recoil starter to start the engine ESC Throttle Switch ESC THROTTLE STANDARD TURBO ECO 1 2 3 ECO When...

Page 8: ...If there is no display after replacing the battery with new one please contact your dealer b The screen interface displays the contents of 21 22 and 23 2 display interfaces in total NOTE The interfac...

Page 9: ...the contents of 9 displayed with Bluetooth and 10 are also displayed at the same time 5 When the engine switch is in the ON position and the engine is either running or not the screen interface will...

Page 10: ...ngine starts and produces power Ground Earth Terminal The ground terminal on this generator is connected to NON current carrying parts of the generator frame and to each AC outlet Before attaching a g...

Page 11: ...engine in a closed area or it may cause unconsciousness and death within a short time Operate the engine in a well ventilated area The generator has been shipped without engine oil Do not start the en...

Page 12: ...f connecting NOTE You can have multiple devices paired to the device however only one connected at a time APP START APPLE 1 On your Apple device visit the App Store 2 In the App Store search for ILONC...

Page 13: ...electrical equipment 2 Turn the ESC Throttle to the Standard position 3 Disconnect all electrical equipment from the AC socket 4 Manual stopping press and release the start switch button on the contr...

Page 14: ...ed appliance s will shut off and the output indicator green will go OFF Stop engine and investigate the problem Determine if the cause is a short circuit in a connected appliance or an overload correc...

Page 15: ...l gauge 10 Rotate the lock 90 clockwise and close right maintenance door Oil Specification Table Use four stroke oil SAE 10W30 is recommended for regular use However when the average temperature in yo...

Page 16: ...must not be broken or cracked If it is damaged it must be replaced Spark Plug NOTICE Incorrect spark plug can cause damage to the engine To replace or clean the spark plug use the spark plug spanner k...

Page 17: ...l of the battery and tighten the installation bolt 4 Install the battery band 5 Reinstall battery maintenance cover and tighten the bolts NOTICE The generator must not run without the battery maintena...

Page 18: ...NG TRANSPORTATION Before transportation allow the generator set to cool completely To prevent fuel spillage when transporting or during temporary storage the generator should be secured upright in its...

Page 19: ...ut 15 ml of oil into the cylinder Turn the Engine Switch to the OFF position Crank the engine by pulling the manual recoil starter a few times to lubricate the cylinder Refit the spark plug and mainte...

Page 20: ...Capacity 1 45 litres Spark Model No NGK BPR7ES Starting mode Recoil start Electric start APP start Generator Length x Width x Height 950x765x773 mm Wheel Solid 2 x 250mm Net weight 130kg WIRING DIAGR...

Page 21: ...659 PO Box 352 BENTLEY WA 6982 Email reception crommelins com au www crommelins com au Crommelins Operations Pty Ltd trading as Crommelins Machinery The Crommelin Group and Crommelins Australia ABN 11...

Reviews: