Operation & Instruction Manual 

 

 

12.

 

  PREPARATION FOR STORAGE 

 
The following procedures should be followed prior to storage of your generator for periods of 6 
months or longer. 
 

 

Drain fuel from fuel tank carefully by disconnecting the fuel line. Gasoline/diesel left in the 
fuel tank will eventually deteriorate making engine starting difficult. 

 

Remove the carburettor float chamber and also drain the carburettor. 

 

Change engine oil. 

 

Check for loose bolts and screws, tighten them if necessary. 

 

Clean generator thoroughly with oiled cloth. Spray with preservative if available. (NEVER USE 
WATER TO CLEAN GENERATOR) 

 

Pull starter handle until resistance is felt, leaving handle in that position. 

 

Store generator in a well ventilated, low humidity area. 

 
 

13.

 

  TROUBLE SHOOTING 

 
When generator engine fails to start after several attempts, or if no electricity is available at the 
output socket, check the following chart. If your generator still fails to start or generate electricity, 
contact your nearest SUBARU engine dealer or service agent for further information or corrective 
procedures. To locate your nearest service agent go to www.crommelins.com.au. 
 

When Engine Fails to Start: 
 

Check if choke lever is in its proper position. 

 

Set the choke lever to “CLOSE” position. 

Check if fuel valve is open. 

If closed, open fuel valve. 

Check fuel level. 

If empty, refill fuel tank making sure not to overfill. 

Check if engine switch if in OFF position. 

Turn engine switch to “ON”. 

Check to make sure generator is not connected to an 
appliance. 

If connected, turn off the power switch on the 
connected appliance and unplug. 

Check spark plug for loose spark plug cap. 

If loose, push spark plug cap back into place. 

Check spark plug for contamination. 

Remove spark plug and clean electrode. 

 
NO Electricity Is Generated at Receptacle: 

 

Check to make sure AC circuit breaker is in the “ON” 
position. 

After making sure that the total wattage of the 
electrical appliance is within permissible limits and 
there are no defects in the appliance, turn the AC 
circuit breaker to the “ON” position. If breakers 
continue to actuate, consult your nearest service 
agent. 

Check AC receptacle and DC terminals for loose 
connection. 

Carbon brushes are excessively worn. 

Check to see if engine starting was attempted with 
appliances already connected to generator. 

Turn off switch on the appliance, and disconnect 
cable from receptacle. Reconnect after generator 
has been started properly. 

Low power. 

Carbon brushes are excessively worn. 

 

Summary of Contents for 1B40

Page 1: ...tenance CROMMELINS suggest that you retain this manual for ready reference regarding proper handling of CROMMELINS Generator CROMMELINS GENERATORS Spare Parts Service Phone 1300 554 524 Freecall Fax 1...

Page 2: ...r s manual at hand so that you can refer to it at anytime Due to constant efforts to improve our products certain procedures and specifications are subject to change without notice When ordering spare...

Page 3: ...ed in the exhaust gases will endanger human lives Operate generator only outdoors and far from open windows doors ventilation intakes and other openings Keep the generator at least 1 meter 3 feet away...

Page 4: ...ell away from generator area Be very careful not to touch any parts of the hot engine especially the muffler area or serious burns may result Keep children and all bystanders at a safe distance from w...

Page 5: ...5 CROMMELINS GENERATOR Operation Instruction Manual...

Page 6: ...on the fuel filter neck Make sure you review each of the warnings in order to prevent fire hazard Do not refill tank while engine is running or hot Before filling fuel turn the engine switch into fuel...

Page 7: ...or more Size Less than 185 L x 125 W x 150 H mm Death personal injury and or property damage may occur unless instructions are followed carefully Use battery of recommended capacity Turn the starter...

Page 8: ...engine fails to start return the key to the I on position and wait about 10 second then start again Do not turn the key switch to start position when the engine is running to prevent damage of starti...

Page 9: ...maintain use Loads such as fluorescent lamps require 1 2 to 2 times the indicated wattage during start up Loads for mercury lamps require 2 to 3 times the indicated wattage during start up Electrical...

Page 10: ...ent mL 169 211 404 404 404 479 Fuel Automotive Unleaded Gasoline Fuel tank capacity L 12 8 16 6 1 7 0 22 0 27 5 1 8 4 Engine oil capacity L 0 6 1 2 1 2 1 7 Rated continuous operation H 10 5 9 0 8 5 7...

Page 11: ...e SUBARU Air cooled 4 stroke overhead valve diesel engine Hatz diesel engine Kohler diesel engine Displacement mL 265 412 462 505 Fuel Automotive Diesel Fuel tank capacity L 3 2 4 5 5 0 Engine oil cap...

Page 12: ...button Anderson jump start plug Lockable battery isolator Recoil lockout Bunding 1kg fire extinguisher Recoil lockout Anderson jump start plug options vary depending on mine site CENTRAL LIFTING BAR R...

Page 13: ...500 HOURS Replace spark plug and cleaner element Clean and adjust carburettor valve clearance and valve seat along with cylinder head EVERY 1000 HOURS 24 MTHS Inspect control panel parts Check rotor a...

Page 14: ...ed or inadequate elements causes damage and wears out the engine Always keep the element clean a Remove the bolt of air cleaner cover b Remove the air cleaner cover and cleaner element c Urethane foam...

Page 15: ...gine switch normally operated No leakage of engine oil and fuel gasoline diesel 11 TRANSPORTING When transporting the generator make sure that the fuel gasoline diesel is drained from the tank To prev...

Page 16: ...crommelins com au When Engine Fails to Start Check if choke lever is in its proper position Set the choke lever to CLOSE position Check if fuel valve is open If closed open fuel valve Check fuel level...

Reviews: