LPT-P - Operation Manual
Rev. B | 2018.08
5.5.2 Enclosure Bottom
NUMBER
FEATURE
Œ
Door Hinge
•
1/2” Conduit Entry Knockout
5.6 Wiring Connections
The LPT-P digital transmitter is a low voltage powered device. Any application of operating voltages
higher than indic
ated in the specifi cation may result in damage. Double check wiring connections
prior to powering the transmitter. Damage from incorrect wiring connections or from too much
voltage applied is not covered under warranty.
All wiring should be run in EMT (or better) conduit properly earth grounded. All communications
(network) wiring must be in shielded cabling. The shield should be connected to earth ground close
to the primary supply connection only, and must have a contiguous connection throughout the
network. Communication uses a daisy chain confi guration. The recommended 4 conductor, 16 AWG,
shielded stranded wire cable types are AlphaWire 79220, Belden 9954 or equivalent.