25
BOOST in OFF position
U out
charger
t
0
U floating
0
I out
charger
t
I nom
3.3.5.
Indicators
INDICATOR
STATE
MEANING
Green "ON"
On
- Charger is ON
Off
or
or
- No or poor quality AC current
- Input fuse blown
- Internal charger malfunction
Yellow "Boost / Absorption"
On
or
- SW1 Switch:
Boost in OFF position
- SW1 switch:
Boost in ON position and Boost/Absorption phase
completed
Flashing
- SW1 Switch:
Boost in ON position and charger in the
Boost/Absorption phase
Off
or
- Internal charger malfunction
- Output fuse blown
Yellow "Floating"
On
Charger current < 15% rated current (floating phase)
Off
Charger current > 15% rated current
These indicators are visible from the front of the appliance through the light guides, thereby allowing
operation of the appliance to be monitored.
4.
EQUIPMENT MAINTENANCE AND REPAIRS
4.1.
O
VERVIEW
This paragraph deals with equipment maintenance and repairs. Proper operation of the product and its
service life are dependent on strict compliance with the following recommendations.
4.2.
E
QUIPMENT MAINTENANCE
Disconnect the battery charger from the AC network before starting any maintenance work.
If appliances are in a dusty atmosphere, vacuum-clean them regularly, since dust deposits may adversely
affect heat release.
Check the state of battery charge every 3 months.
The tightness of nuts and screws should be checked annually to ensure efficient operation of the appliance
(particularly in hostile conditions: vibrations, shocks, high variations in temperature etc.).
A full technical inspection by a CRISTEC-accredited engineer is recommended every five years. It can also
be done at our plant.
With this setting, the CPS3 charger produces a single-stage UI
type load curve. It generates a constant voltage, supplying the
current required by the battery(ies). Recharging time depends on
the state of the battery, being longer than when the boost is in the
ON position.