Set the Shade Limits

If necessary, set the lower and upper shade limits. If the shade limits are
not set, the red LED flashes three times, pauses for 1 second, flashes
once, pauses for 5 seconds, and then repeats this code until the limits are
set.

NOTES:

l

Limit Setup mode exits after 8 seconds of inactivity.

l

If a limit is not set after the upper or lower limit is saved, the motor
automatically enters Limit Setup mode for the opposite limit. This
typically occurs after the motor direction has been reversed and both
limits are erased.

l

For Crestron Horizontal Sheers, the lower limit is defined as the point
before the hem bar tilts.

Set the lower limit for the shade:

1. Press and hold the SET button for 4 seconds to enter Limit

Setup mode. The LED alternates between amber and green.

2. Press and release the DN button to begin lower limit setup. The green

LED flashes.

3. Use the UP and DN buttons to set the shade to its desired position.

4. Press and hold SET for 4 seconds. The LED turns solid red to confirm

that the lower limit was successfully set.

Set the upper limit for the shade:

1. Press and hold SET for 4 seconds to enter Limit Setup mode. The LED

alternates between amber and green.

2. Press and release the UP button to begin upper limit setup. The amber

LED flashes.

3. Use the UP and DN buttons to set the shade to its desired position.

4. Press and hold SET for 4 seconds. The LED turns solid red to confirm

that the upper limit was successfully set.

Joining an infiNET EX® Network (infiNET EX
Interfaces Only)

The device connects to the Crestron network via the infiNET EX
communications protocol. Use the procedures outlined below to join or
leave an infiNET EX network and to verify communications between the
device and the control system.

Joining an infiNET EX Network

Before a device can be used in a lighting system, it must first join an
infiNET EX network by being acquired.

NOTE:

A device can be acquired by only one gateway.

1. Put the infiNET EX gateway into Acquire mode from the unit itself or

from Crestron Toolbox, as described in its manual at

www.crestron.com/manuals

.

NOTE:

In an environment where multiple gateways are installed, only

one gateway should be in Acquire mode at any time.

2. Place the device into Acquire mode.

a. Press the SET button three times, and then press and hold it down

(tap-tap-tap-press+hold) until the white LED on the device flashes
once (this can take up to 10 seconds).

b. Release the button to start the acquire process. The LED flashes

slowly to show that the device is actively scanning the infiNET EX
network.

l

The LED turns on for 5 seconds to show that the device has
been successfully acquired to the infiNET EX network.

l

The LED flashes quickly to indicate that the device was not
successfully acquired by the infiNET EX network. Press the
SET button to acknowledge failure to acquire the infiNET EX
network. Ensure the gateway is in Acquire mode and within
range before attempting the acquire process again.

10

CSA-DECOR3 Series

Quick Start

Shade Motor Bracket Installation and Motor Programming

Summary of Contents for CSA-DECOR3 Series

Page 1: ...masonry installations It is the responsibility of the installer to make sure that the mounting method used is secure l Ensure that all mounting brackets are level and on the same plane l All shades m...

Page 2: ...right side of the window opening l The motor bracket mounts on the left side of the window opening NOTES l The stamped L and R should face the wall and window l For inside mounts secure the mounting...

Page 3: ...idler pin into the top of the keyhole on the right bracket and slide it down into the keyhole The idler pin sits on the vertical adjustment screw Insert the Idler Pin into the Keyhole 2 Raise the mot...

Page 4: ...air is coming in through a window l A foreign object is stuck to the shade fabric for example tape bugs dust etc Ways to prevent telescoping l Use the leveling features built into the shade brackets t...

Page 5: ...d on mounting location Swapping the hardware requires a Phillips screwdriver Left Side Idler Bracket Wall Mount Right Side Idler Bracket Wall Mount Left or Right Side Idler Bracket Ceiling or Header M...

Page 6: ...otate Keyhole Right Side Wall Mount to Ceiling Mount Rotate Keyhole Right Side Wall Mount to Left Side Wall Mount 6 CSA DECOR3 Series Quick Start Shade Motor Bracket Installation and Motor Programming...

Page 7: ...the Cables To ensure proper functionality and a clean look consider the following when routing cables and making connections l The cables should exit the wall near the motor end of the shade assembly...

Page 8: ...erformed remotely using a control system The timeout and LED indicators are the same as described in this document Controls and Indicators The Crestron CSM I QMTDC shade motors have UP SET and DN down...

Page 9: ...the shade hangs level and plumb Upon startup run the shade all the way down and check for plumb Observe the shade closely as it rolls up If the shade begins to telescope stop immediately and take the...

Page 10: ...upper limit was successfully set Joining an infiNET EX Network infiNET EX Interfaces Only The device connects to the Crestron network via the infiNET EX communications protocol Use the procedures out...

Page 11: ...s to provide a visual reference that the motor is operating normally or if it is in an error state Normal Operation The following table provides a list of possible LED patterns encountered during norm...

Page 12: ...The motor is not being polled by the control system Ensure that the Net ID matches the control system program and that the program is running on the control system Troubleshooting The following table...

Page 13: ...is licensed to Crestron dealers CSPs and end users under a separate End User License Agreement Both of these Agreements can be found on the Crestron website at www crestron com legal software_license...

Reviews: