Crestron
CHV-TSTAT and CHV-THSTAT
Thermostats
Viewport Error Log Message Formats
When a remote sensor that has been designated as USE, SLAB, or OD in the Setup
Sensors screen generates an error, a message is sent to the error log. Retrieve this
message using Viewport,
Function | 2-Series | Error Log | Show Error Log
.
Error Message Format
Sensor <channel> type <designator> <CHA errors>, <CHB
errors> Errors @ <cycle count>
Where:
channel
is the sensor channel string
designator
is the sensor setup designation
CHA errors/CHB
errors
are the number of errors on each sub-channel
cycle count
is the number of read cycles that have occurred.
NOTE:
Both sub-channels have their error count reported, regardless of the sensors
connected.
This message is sent upon the first error on the channel, as well as every 100 errors
thereafter. The following is an example output, as seen in Viewport, when a single
OD sensor on channel one fails.
Error: Message from device Slot-09.ID-2A: Sensor R1T
type OD: 2,3 Errors @ 3922 (0056:0000:0056)
Operations and Installation Guide – DOC. 8163C
Thermostats: CHV-TSTAT and CHV-THSTAT
•
83