Thermostats Crestron
CHV-TSTAT and CHV-THSTAT
Heat/Cool, 1 or 2 Stages, Forced Air or Radiant (continued)
OTHER SETTINGS
SETUP:
OTHER SETTINGS
Wide Range Cool:
Run Fan in Ht Calls:
Auto DdBand Deg:
Disable Auto Mode:
N
N
2
0
N
EXTENDED COOL SETPOINT
RANGE 38-99F (3-37C)
Wide Range Cool:
Extends cool setpoint to full
auto range of 38 to 99 degrees F.
Run Fan in Heat Calls:
Most heating systems run
the fan automatically. If your heating system
requires fan control, select Yes.
Auto Mode Dead Band:
(valid selections are 2
through 6) The minimum differential between
heating and cooling setpoints (Dual Setpoint Auto
set to Yes in Display Options).
Disable Auto Mode:
Will not display Auto on
System Mode screen and will not permit entering
the auto mode even from Cresnet commands.
SENSORS
SETUP: SENSORS
Sensor
Internal:
Remote 1:
Remote 2:
>TEMP HUM
USE OMIT
SLAB
DETECTED: 1 x T
Choose
USE
or
OMIT
(Built-in Sensors Only).
Choose Use to permit temperature averaging. Sensor
Temp/Humidity can be output to network even if Omit
is chosen.
Choose
USE
,
OMIT
,
OD
(outdoors), or
SLAB
(Remote Sensors Only)
NOTE:
Remote 1 and Remote 2 options do not
appear on this screen if these sensors are not
connected.
NOTE:
Thermostat auto-detects connected remote
sensors.
SERVICE/TEST
SETUP: SERVICE/TEST
Heat Call:
Cool Call:
Humidifier Call:
Fan Run Call:
OFF
OFF
OFF
OFF
NOTE:
This screen bypasses all system delays
and is used by the installer to manually operate
the HVAC system. Only one system can be run at
a time.
Press
MODE
button to return to the first screen
Or
Press and hold the
MODE
and
VIEW
buttons
simultaneously for five seconds to exit Setup.
NOTE:
You cannot exit if the sensor setup does not
meet system requirements.
30
•
Thermostats: CHV-TSTAT and CHV-THSTAT
Operations and Installation Guide – DOC. 8163C