Thermostats Crestron
CHV-TSTAT and CHV-THSTAT
Heat/Cool, 1 or 2 Stages, Forced Air or Radiant
Press and hold the
MODE
and
VIEW
buttons simultaneously for five seconds to
enter setup.
SETUP SYSTEM
SETUP: SYSTEM
Heat Sys Type:
# Heat Stages:
# Cool Stages:
Radiant / F. Air:
H/C
2
2
F.Air
SEPARATE HEAT AND COOL
System Type:
H/C
Heat/Cool.
One or two heat and cool stages.
Radiant or Forced Air Heat.
SYSTEM
PERFORMANCE
SETUP: SYSTEM PERF
Heat Anticipator:
Cool Anticipator:
Intrstg Differential:
5
2
2.0
0
Anticipators:
(1 through 6)
Low number = more frequent cycles and faster
response (tighter regulation).
High number = less frequent cycles and slower
response (looser regulation).
Interstage Differential:
0.5 to 8.0ºF. The
proportional temperature error to trigger the
second stage.
HUMIDIFIER OPTIONS
SETUP: HUM OPTS
Show Hum Mode Pg:
Show Hum View Pg:
Cold Weather Comp:
Y
Y
N
SYSTEM ENABLE/DISABLE
PAGE
Show Hum Mode Pg
and
Show Hum View Pg:
Select Y to show humidity page in normal operation.
Cold Weather Compensation:
Modifies the
humidifier output to prevent condensation on the
windows. Requires an outdoor temperature source
(CHV-THSAT, or CHV-TSTAT with CHV-RTHS,
CHV-RTS, or CHV-RSS).
Continued on following page.
28
•
Thermostats: CHV-TSTAT and CHV-THSTAT
Operations and Installation Guide – DOC. 8163C