25
Creotech Instruments S.A.
tel. +48 22 233 10 27
ul. Gen. L. Okulickiego 7/9
e-mail: [email protected]
05-500 Piaseczno, Polska www.creotech.pl
3.9
SNMP protocol
In firmware version 1.34 Telnet protocol has been replaced with expanded version of SNMP
protocol. If there is a need to use the Telnet protocol, you should downgrade firmware to version
1.32 (section 3.5). Both the firmware can be found on the website: www.creotech.pl
Firmware 1.32 – Basic SNMP and Telnet
Firmware 1.34 and higher – Expanded SNMP and no Telnet
IP Power Strip lets you communicate with it using the SNMPv2 protocol.
Select the Configuration tab and from the menu on the left, an SNMP group.
You can set permissions to read and write, and view the MIB file.
Using SNMP, you can change, and check the status of the outputs.
Commands for Firmware 1.34 and higher
OID
Type
Description
Device Reset
.1.3.6.1.4.1.39525.1
INTEGER
Set to positive value to reset
Device info
.1.3.6.1.4.1.39525.5.4
DisplayString Get device serial number
.1.3.6.1.4.1.39525.5.5
DisplayString Get device firmware
.1.3.6.1.4.1.39525.5.6
DisplayString Get device product ID
Networking
.1.3.6.1.4.1.39525.5.8.1.1
ENUM
Get & Set IP request method static(0),
dhcp(1)
.1.3.6.1.4.1.39525.5.8.1.2
OCTET STRING Get & Set IP
.1.3.6.1.4.1.39525.5.8.1.3
OCTET STRING Get & Set subnet mask
.1.3.6.1.4.1.39525.5.8.1.4
OCTET STRING Get & Set gateway
.1.3.6.1.4.1.39525.5.8.1.5.[1|2]
OCTET STRING Get & Set DNS entries (2 rows)
.1.3.6.1.4.1.39525.5.8.1.6
OCTET STRING Get device MAC
Measurements (CTI-PS6-M only)
.1.3.6.1.4.1.39525.5.9.2.1.1.1.1.[1-6] INTERGER
Get power outlet voltage RMS
.1.3.6.1.4.1.39525.5.9.2.1.1.1.2.[1-6] INTERGER
Get power outlet current RMS