ELECTRICAL CONNECTIONS- 

NOTE: 

The emergency driver must be fed 

from the same branch as the AC Driver.

STEP 1:

Using customer supplied 90°C minimum rated wire 
connectors, make the following electrical connections: 

a.  Connect the black luminaire lead to 

the unswitched voltage supply lead. 

b.  Connect the white/red luminaire 

lead to the supply switched hot.

c.  Connect white luminaire lead to 

the neutral supply lead.

d.  Connect ground green/yellow wire 

lead to the supply ground lead.

e.  If 0/1-10V Dimming is used, connect 

the violet lead to the supply positive 
dimming lead. If dimming is not being 
used ensure to cap off the violet lead.

f.  If 0/1-10V Dimming is used, connect 

the grey lead to the supply negative 
dimming lead. If dimming is not being 
used ensure to cap off the grey lead.

STEP 2:

Locate the two red leads coming off of the Emergency 
Driver and connect them using supplied connector. 
See 

Figure 2 

on page 1.

WHITE

DIM (-) GREY

DIM (+) VIOLET

NEUTRAL

VIOLET

GREY

SUPPL

Y WIRING

(DIMMING OPTIONAL)

LUMINAIRE

GROUND

GREEN/YELLOW

WHITE/RED

SWITCHED HOT

BLACK

UNSWITCHED HOT

GREEN/YELLOW

GROUND

STEP 4:

Bring customer supply wires into luminaire through the wiring 
knockouts on the backside 

(E) 

or on the end caps and make electrical 

connections per 

“ELECTRICAL CONNECTION”

 section. See 

Figure 3.

NOTE: 

When connecting multiple luminaires together bring leads from 

adjoining luminaire into first luminaire through the end cap wiring 
knockouts and make wiring connections per electrical code. See 

Figure 4.
NOTE:

 If dimming is an option make electrical connection for dimming 

in the dimming compartment. See 

Figure 4.

STEP 5:

Reattach lens and metal lens frame assembly to luminaire base by 
connecting the plug together shown in 

Figure 2

 and carefully push and 

metal lens frame assembly up into the base until it snaps in place. 

EMERGENCY DRIVER CHECK

NOTE:

 For short-term testing of the emergency function, the battery 

must be charged for at least one hour. The emergency driver must be 
charged for at least 24 hours before conducting a long-term test.

STEP 1: 

When AC power is applied, the charging indicator light is illuminated, 
indicating the battery is being charged. When power fails, the 
emergency driver automatically switches to emergency power, 
operating the LED array. When AC power is restored, the emergency 
driver returns to the charging mode.

STEP 2:

Although no routine maintenance is required to keep the emergency 
driver functional, it should be checked periodically to ensure that it is 
working. The following schedule is recommended: 

•  Visually inspect the charging indicator light monthly. It should be 

illuminated. 

•  Test the emergency operation of the fixture at 30-day intervals 

for a minimum of 30 seconds. When the test switch is depressed, 
the LED array should operate. 

•  Conduct a 90-minute discharge test once a year. The LED array 

should operate for at least 90 minutes.

If the luminaire fails any of these checks, consult service personnel.
REFER ANY SERVICING INDICATED BY THESE CHECKS TO 
QUALIFIED PERSONNEL
EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE 
SAME BRANCH CIRCUIT

Summary of Contents for LS Series

Page 1: ...ocal Si vous n êtes pas familier avec ces codes et ces exigences veuillez contacter un électricien qualifié 3 To reduce the risk of electric shock disconnect both standard and emergency power supplies and converter connector of the emergency driver before servicing Pour réduire le risque de décharge électrique vous devez déconnecter à la fois le disjoncteur divisionnaire ou les fusibles et les ali...

Page 2: ...embly is removed If the lens frame needs to be removed in the future once pull tabs have been discarded then use a non marring tool or by hand and release the rivet catch on each end of the luminaire After releasing rivet catches See Figure 1 2 and to the righ NOTE The lens and metal lens frame is a single assembly and does not come apart DO NOT attempt to remove the lens from the metal lens frame...

Page 3: ...stomer supplied T Bar clips to the designated opening on the luminaire as shown in Figure 3 Bring luminaire into T Bar ceiling grid and secure luminaire to grid NOTE 8 luminaires will have 4 designated openings for customer supplied T Bar clips D Chain Mounting Attach 2 customer supplied V hooks to each end of the luminaire base Attach customer supplied chain to the V hooks and mounting surface Se...

Page 4: ...g multiple luminaires together bring leads from adjoining luminaire into first luminaire through the end cap wiring knockouts and make wiring connections per electrical code See Figure 4 NOTE If dimming is an option make electrical connection for dimming in the dimming compartment See Figure 4 STEP 5 Reattach lens and metal lens frame assembly to luminaire base by connecting the plug together show...

Reviews: