background image

 

1. Disconnect AC power before servicing.
2. Refer to wiring diagram for proper connections.
3. All servicing should be performed by qualified personnel.
4. Consult your local building code for approved wiring and  installation.
5. Do not use this equipment for other than intended use.
6. Do not let power cords touch hot surfaces.

7. Mount and secure the fixture at a location and height  to avoid ready access  
and tampering by unauthorized persons.
8. The use of accessory equipment is not recommended by the manufacturer 
and may cause an unsafe condition.
9. Suitable for wet locations. See product label for temperature limitations.

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

SUITABLE FOR WET LOCATIONS

AMBIENT TEMPERATURE LIMITS:

Standard "BB" models: -20º C to +40º C

High Temp "BB" models (SW): -20º C to +45º C

Remote models: -40º C to +50º C

J- Box and Supply Wiring

1. See above. Assemble  standard 4” x 4” deep j-box with 1 ½” extension. Note available knock-outs for 
wiring. Remove K.O's in areas shown for wiring and connecters. 

2. Align edge of extension flush or just below finish panel surface.

3. 

SECURITY LIGHTING SWITCH CONTROL (OPTION -SW)

AVAILABLE K.O.'S
4 PLACES

SET EDGE OF BOX
FLUSH TO WALL 
FINISH OR
PANEL THICKNESS

STANDARD J-BOX
4 x 4 x 21/8"

EXTENSION  RING
4 x 4 x 11/2"

ITEM   QTY   P/N  

DESCRIPTION

 

1  

1  

346302   CANOPY POWER ASSBY

2  

1  

206110   BATTERY PACK 3.6V

3  

1  

206117

 

BATTERY PACK 4.8V

 

 

 

4  

1  

346200

LAMP HOUSING ASSBY

2 3

LAMP 
PLUG

4

L N G

120/277 VAC

BUILDING SUPPLY

Black

Red

White

1

OPTIONAL NORMAL ON 

CONTROL SWITCH WIRING

GROUND
TO J-BOX

INSTALLATION INSTRUCTIONS AND OWNER'S MANUAL

LED Architectural Emergency Light with Battery Backup

Series MAEBB

Moonlite LED

 5.15.03

 

 

 

SEC CONTROL INPUT VOLTS
STANDARD FIXTURE = 120 VAC 
DG FIXTURE = 120/ 277 VAC UNIVERSAL

BATT

L

N

LAMPS

RED
(LINE)

BLACK

WHITE

SEC CONTROL
MAKE- SEC ON
BREAK- SEC OFF

120 / 277 VAC

UN- SWITCHED NORMAL INPUT

POWER

SUPPLY