background image

16

TROUBLE SHOOTING

CAUTION !

 Always disconnect the pump from the electrical power source before handling.

If the system fails to operate properly, carefully read instructions and perform maintenance recommendations.
If operating problems persist, the following chart may be of assistance in identifying and correcting them:

MATCH “CAUSE” NUMBER WITH CORRELATING “CORRECTION” NUMBER

.

NOTE:

 Not all problems and corrections will apply to each pump model.

PROBLEM

CAUSE

CORRECTION

Pump will not run

1.

 Poor electrical connection, blown fuse, 

tripped breaker or other interruption of power, 
improper power supply.

2.

 Motor or switch inoperative (to isolate 

cause, go to manual operation of pump).

2a.

 Flaot movement restricted.

2b. Switch will not activate pump or is defec-
tive.

3.

 Insuffi cient liquid level.

1. Check all electrical connections for 
security. Have electrician measure current 
in motor leads, if current is within ±20% 
of locked rotor Amps, impeller is probably 
locked. If current is 0, overload may be 
tripped. Remove power, allow pump to cool, 
then recheck current.
2a. Reposition pump or clean basin as 
required to provide adequate clearance for 

fl oat.
2b. Disconnect level control. Set ohmmeter 
for a low range, such as 100 ohms full scale 
and connect to level control leads. Actuate 
level control manually and check to see that 
ohmmeter shows zero ohms for closed switch 
and full scale for open switch. (Float Switch).
3. Make sure liquid level is at least equal to 
suggested turn-on point.
4. Recheck all sizing calculations to 
determine proper pump size.
5. Check discharge line for restrictions, 
including ice if line passes through or into 
cold areas.
6. Remove and examine check valve for 
proper installation and freedom of operation.
7. Open valve.
8. Check cutter for freedom of operation, 
security and condition. Clean cutter and inlet 
of any obstruction.
9. Loosen union slightly to allow trapped air 
to escape.Verify that turn-off level of switch 
is set so that the suction is always fl ooded. 
Clean vent hole.
10. Remove & examine for damage. Replace 
pump stator if required.
11. Repair fi xtures as required to eliminate 
leakage.
12. Check pump temperature limits & fl uid 
temperature.
13. Replace portion of discharge pipe with 
fl exible connector.
14. Turn to automatic position.
15. Check for leaks around basin inlet and 
outlets.

Pump will not turn off

2a. Float movement restricted.
2b. Switch will not activate pump or is defec-
tive.
4. Excessive infl ow or pump not properly sized 
for application.
9. Pump may be airlocked.
14. H-O-A switch  on panel is in “HAND” posi-
tion

Pump hums but does not run

1. Incorrect voltage
8. Cutter jammed or loose on shaft, worn or 
damaged, inlet plugged.

Pump delivers insuffi cient capacity

1. Incorrect voltage.
4. Excessive infl ow or pump not properly sized 
for application.
5. Discharge restricted.
6. Check valve stuck closed or installed 
backwards.
7. Shut-off valve closed.
8. Cutter jammed or loose on shaft, worn or 
damaged, inlet plugged.
9. Pump may be airlocked.
10. Pump stator damaged/torn.

Pump cycles too frequently or runs 
periodically when fi xtures are not in use

6. Check valve stuck closed or installed 
backwards.
11. Fixtures are leaking.
15. Ground water entering basin.

Pump shuts off and turns on indepen-
dent of switch, (trips thermal overload 
protector). 

CAUTION!

  Pump may start 

unexpectedly. Disconnect power supply.

1. Incorrect voltage.
4. Excessive infl ow or pump not properly sized 
for application.
8. Cutter jammed, loose on shaft, worn or 
damaged, inlet plugged.
12. Excessive water temperature.

Pump operates noisily or vibrates 
excessively

4. Operating at too high a pressure.
5. Discharge restricted.
8. Cutter broken.
13. Piping attachments to buiding structure too 
rigid or too loose.

Summary of Contents for 104189

Page 1: ...provement program product changes may occur As such Crane Pumps Systems reserves the right to change product without prior written notification 420 Third Street 83 West Drive Bramton Piqua Ohio 45356 Ontario Canada L6T 2J6 Phone 937 778 8947 Phone 905 457 6223 Fax 937 773 7157 Fax 905 457 2650 www cranepumps com Form No 115941 Rev N Series 2SEV 3SEV L DS 1 5 2 HP 3450 RPM 60 Hz Single and Double S...

Page 2: ...Fig 16 18 DOUBLE SEAL CROSS SECTION Fig 17 19 DOUBLE SEAL EXPLODED VIEW Fig 18 20 PARTS LIST 21 22 RETURNED GOODS POLICY 23 WARRANT START UP REPORT WARRANTY REGISTRATION SPECIAL TOOLS AND EQUIPMENT INSULATION TESTER MEGGER DIELECTRIC TESTER SEAL TOOL KIT see parts list PRESSURE GAUGE KIT see parts list Other brand and product names are trademarks or registered trademarks of their respective holder...

Page 3: ...ert fingers in pump with power connected Always wear eye protection when working on pumps Make sure lifting handles are securely fastened each time before lifting DO NOT operate pump without safety devices in place Always replace safety devices that have been removed during service or repair Secure the pump in its operating position so it can not tip over fall or slide DO NOT exceed manufacturers ...

Page 4: ...PT 30 Ft 9 1m Cord Quick connect Custom molded for sealing and strain relief SPEED 3450 RPM 60Hz nominal UPPER BEARING Design Single Row Ball Oil Lubricated Load Radial LOWER BEARING Design Single Row Ball Oil Lubricated Load Radial Thrust MOTOR Design NEMA L Single phase NEMA B Three Phase Torque Curve Oil Filled Squirrel Cage Induction Insulation Class B Class F on selected models SINGLE PHASE P...

Page 5: ...5 inches mm 2SEV DS Series 3SEV L Series 3SEV DS Series ...

Page 6: ...tion or basin shall be vented in accordance with local plumbing codes This pump is designed to pump sewage effluent or other nonexplosive or noncorrosive wastewater and shall NOT be installed in locations classified as hazardous in accordance with the National Electrical Code NEC ANSI NFPA 70 or the Canadian Electrical Code CEC Never install the pump in a trench ditch or hole with a dirt bottom th...

Page 7: ...sent It is recommended that this detector be connected in series to an alarm device or the motor started coil to alert the operator that a moisture detect has occurred In the event of a moisture detect check the individual moisture sensor probe leads for continuity resistance no moisture and the junction box control box for moisture content The above situations may induce a false signal in the moi...

Page 8: ...5 480 3 60 3450 F B 4 9 13 5 14 4 SOW 0 60 15 2 17 0 3SEV1552L 1 5 600 3 60 3450 F B 3 9 11 0 14 4 SOW 0 60 15 2 22 2 3SEV2022L 2 0 240 1 60 3450 C B 16 0 42 0 12 3 SOW 0 61 15 5 1 26 55 34 3SEV2092L 2 0 200 240 3 60 3450 J B 13 2 12 30 0 14 4 SOW 0 60 15 2 3 08 3SEV2042L 2 0 480 3 60 3450 J B 6 0 15 0 14 4 SOW 0 60 15 2 12 30 3SEV2052L 2 0 600 3 60 3450 J B 4 8 12 0 14 4 SOW 0 60 15 2 19 70 3SEV1...

Page 9: ... 1 3 After leak is repaired dispose of old oil properly and refill with new oil as per section F 1 4 F 1 3 Pressure Test Pumps that have been disassembled Motor Housing If the pump has been disassembled the oil should be drained before a pressure test as described in section F 1 1 Remove pipe plug 39 from motor housing 6 Apply pipe sealant to pressure gauge assembly and tighten into hole See Figur...

Page 10: ...assembly To install impeller 33 clean the threads with thread locking compound cleaner Apply removable Loctite 603 or equivalent to shaft threads Screw impeller onto the shaft hand tight while using a screwdriver in the slot at the end of the shaft to hold it stationary Apply thread locking compound 57 to shaft threads then install jam nut 66 and torque to 40 ft lbs It is important that the spring...

Page 11: ...s of 28a and 28b are together see Figure 8 It is extremely important to keep seal faces clean during assembly Dirt particles lodged between these faces will cause the seal to leak Place spring 28c over shaft and in place on rotating member 28b making sure it is seated on retainer and not cocked or resting on bellows tail Slide retaining ring 28d over shaft and let rest on spring 28c Replace snap r...

Page 12: ...y F 4 2 Reassembly Moisture Sensors DS Models If pump is equipped with optional moisture sensors reassemble by applying thread compound to threads on probes 4 and install in upper seal plate 5 see Figures 17 and 18 Connect wire assemblies 53 to probes 4 with washers 46 and machine screws 45 Thermal Sensors If pump is equipped with optional thermal sensors use terminal connectors 52 to connect wire...

Page 13: ...ower Control Cord Refill the cooling oil as outlined in paragraph F 1 3 Make wire connections as outlined in paragraph F 4 3 Insert female end of cord plug into housing bore aligning timing mark with hole in terminal block 21 see Figure 13 Compress cord plug with compression flange 16a by tightening hex bolts 11 into the housing 6 Torque to 132 in lbs FIGURE 12 FIGURE 14 SINGLE PHASE 240 VOLT AC PS...

Page 14: ...14 FIGURE 14 CONTIUED ...

Page 15: ...the design configuration This number is used for ordering and obtaining information G 3 MODEL NUMBER This designation consists of numbers and letters which represent the discharge size series horsepower motor phase and voltage speed and pump design This number is used for ordering and obtaining information G 4 SERIAL NUMBER The serial number block will consist of a six digit number which is specific...

Page 16: ... cutter for freedom of operation security and condition Clean cutter and inlet of any obstruction 9 Loosen union slightly to allow trapped air to escape Verify that turn off level of switch is set so that the suction is always flooded Clean vent hole 10 Remove examine for damage Replace pump stator if required 11 Repair fixtures as required to eliminate leakage 12 Check pump temperature limits flu...

Page 17: ...17 FIGURE 15 2SEV L 3SEV L Series Single Seal ...

Page 18: ...18 FIGURE 16 2SEV L 3SEV L Series Single Seal ...

Page 19: ...19 FIGURE 17 2SEV DS 3SEV DS Series Double Seal ...

Page 20: ...20 FIGURE 18 2SEV DS 3SEV DS Series Double Seal ...

Page 21: ... 9 1 036391 Capacitor 1 Phase 10 1 039858 Capacitor Bracket 1 Phase 11 4 1 129 1 Hex Hd Cap Screw Std 5 16 18 x 75 Lg Stainless 6 1 129 1 Hex Hd Cap Screw Optional for moisture and temp sensors 12 8 026322 Lockwasher Std 5 16 Stainless 10 026322 Lockwasher Optional for moisture and temp sensors 13 1 103503 Handle 16 1 See Table 2 Power Cord Set 19 1 105197 Snap Ring Std 2 105197 Snap Ring Optional...

Page 22: ...embly 200 240V 3Ph 50 1 051621 Thermal Sensor Optional for temperature sensor Not Shown 51 2 105155 Wire Assembly Optional for temperature sensor Not Shown 52 2 625 00163 Terminal Connector Optional for temperature sensor Not Shown 53 2 105106 Wire Assembly Optional for moisture sensor 54 1 103584 Terminal Block Temperature sensor options 103585 Moisture and temp sensor options 56 1 See Table 2 Co...

Page 23: ...es between the results of eld testing conducted by or for user and laboratory tests corrected for eld performance the latter shall control RECOMMENDATIONS FOR SPECIAL APPLICATIONS OR THOSE RESULTING FROM SYSTEMS ANALYSES AND EVALUATIONS WE CONDUCT WILL BE BASED ON OUR BEST AVAILABLE EXPERIENCE AND PUBLISHED INDUSTRY INFORMATION SUCH RECOMMENDATIONS DO NOT CONSTITUTE A WARRANTY OF SATISFACTORY PERF...

Page 24: ...ent To Insure That Employees Will Not Be Exposed To Health Hazards In Handling Said Material All Applicable Laws And Regulations Shall Apply IMPORTANT WARRANTY REGISTRATION Your product is covered by the enclosed Warranty To complete the Warranty Registration Form go to http www cranepumps com ProductRegistration If you have a claim under the provision of the warranty contact your local Crane Pump...

Reviews: