37
FLUE
OPTIONS
QUINTA ACE 30 AND 45
100MM CONVENTIONAL OR OPEN-FLUE SYSTEMS
The components listed below are only suitable for internal use as illustrated on pages 33 and 34. As the boiler
is fan assisted it makes no difference if the run is horizontal or vertical but the flue should terminate vertically.
Calculation data based on flue products supplied by Remeha. Other distances available at 110mm (see manual) are achievable with increased flue sizes.
Note: All dimensions are in mm.
Note 2: Fall to boiler ≥ 50mm/Mtr.
15mm ID/32mmO/D
100mm
180mm
101 i/d
100 o/d
50
'L'
101 i/d
80 o/d
101 i/d
10
60
200
Top
76
76
105
105
30
20
10
101 i/d
95
25-55mm
15mm ID/32mmO/D
100mm
180mm
101 i/d
100 o/d
50
'L'
101 i/d
80 o/d
101 i/d
10
60
200
Top
76
76
105
105
30
20
10
101 i/d
95
25-55mm
Standard length
‘L’ = 1000mm Part No. MG87062
‘L’ = 500mm Part No. MG87061
‘L’ = 250mm Part No. MG87060
Condensate drain
Part No. MG410085130
Reducer 80mm spigot to 100mm
Part No. MG87127
Must be used on the QACE 30/45 flue socket
connection to adapt to 100mm system
Air Inlet guard
Part No. PU002
90° Bend
Part No. MG87113
45° Bend
Part No. MG87103
Note:
2 x 45° bends will
offset to 71mm centres
Flue terminal c/w bird guard
Part No. PU001
Twin pipe adaptor plate
Part No. S100250
Mounting bracket
Part No. MG87193
8mm x 45mm
screw thread
Silicon seal ring
Part No. MG87183
OPEN-FLUE DATA
QUINTA ACE 30 100MM
QUINTA ACE 45 100MM
Maximum overall flue run
Metres
40
40
Reduction length for each 45° bend
Metres
1.4
1.4
Reduction length for each 90° bend
Metres
4.9
4.9
Cut down to suit diameter of flue in use
and seal with silicone supplied
Detail of standard weathering plate for
100mm to 150mm flue (Part No. VE001)
Standard length
‘L’= 1000mm Part No. MG87062
‘L’= 500mm Part No. MG87061
‘L’= 250mm Part No. MG87060
Reducer 80 spigot to 100 socket
Part No. MG87127
Must be used on the QP 30/45 flue
connection to adapt to 100mm system
Flue terminal c/w bird guard
Part No. PU001
90° bend
Part No. MG87113
Note:
2 x 45° bends will offset
to 71mm centres
45° bend
Part No. MG87103
Air inlet guard
Part No. PU002
Condensate drain
Part No. MG410085130
Mounting bracket
Part No. MG87193
Silicon seal ring
Part No. MG87183
Eccentric flue connector
80/80 – Part No. S100250
100/100 – Part No. S101626
Siphon
Part No. MG410081165
268 ± 3
Siphon adaptor kit
Part No. MG410087491
101 i/d
50
100 o/d
'L
'
125
101 i/d
80 o/d
600mm x 500mm
80 approx
20
30
95
10
101 i/d
101 i/d
Top
10
200
60
76
76
105
105
180mm
100mm
25mm ID/32mmO/D
25-55mm
8mm x 45mm
screw thread
Summary of Contents for Quinta Ace 115
Page 1: ...QUINTA ACE RANGE ...
Page 70: ......