CHPA
S
ERIES
4-4
THIS
DOCUMENT
IS
THE
PROPERTY
OF
COMMUNICATIONS
&
POWER
INDUSTRIES.
REPRODUCTION
OR
RELEASE
WITHOUT
EXPRESS
PERMISSION
IS
STRICTLY
PROHIBITED
D
OC
.01023245
R
EV
.R
3.
When HTD countdown reaches 0:00, verify that the STANDBY LED lights. Reaching this
point in the procedure indicates that the following conditions have been met:
•
Self-tests were successful.
•
The TWT (traveling wave tube) heater is warmed up.
•
No faults have occurred up to this point.
•
The CHPA is ready for the next normal step: Transmission. (
Do not
press the
TRANSMIT button switch at this time.)
4.5 Verifying Operational Settings
The CHPA is delivered with all of its operational values factory preset to meet the requirements
of a typical installation. Before the CHPA is used at the installation site, the user-configurable
settings must be checked and, if necessary, set to meet the user’s requirements.
4.6 Setting the Fault and Alarm Trip Points
The following Fault and Alarm Trip Point settings can be displayed and changed:
•
HELIX Over and Under voltage and current settings
(Factory Authorized Access Code
required; see Appendix B.)
•
LOW RF Alarm set
—A visual alarm for warning operators and for triggering an RF switch
system (refer to “RF Switch System Interface” in Chapter 3).
•
HIGH RF Alarm set
—A visual alarm for warning operators.
•
LOW RF Fault set
—This fault occurs if the RF output power falls below the Low RF Fault
trip point.
•
HIGH RF Fault set
—This fault setting protects the CHPA against using it above the High
RF Fault trip point.
•
RF INHIBIT
–A manual way to inhibit RF output. (Useful in testing.)
Use the following procedures to verify or change the trip points.
To change Helix Over and Under voltages, perform the following steps. (Before checking this
setting, read the portion of Appendix B entitled “Factory Authorized Access Code [FAAC]” —
you will find the FAAC in this section.)
1.
Press the SPECIAL button followed by the . (decimal) button. Key in 15; the display will
change to the entry for the FAAC.
2.
Enter the FAAC, then press ENTER.
3.
Press FUNCTION to enter the Factory Authorized Access Mode (FAAM). The Test Mode
LED will flash to indicate that the unit is in FAAM.