64
POOLDENS
COSMOGAS
15 - USE
Loc 20
Flame lost three times
Check: that the ionisation current is at a value of more
than 4 (follow the procedure in section 16.12)
Check: that the flue gas outlet is suitably protected
from blockages caused by gusts of wind
If the ionisation current is not more than 4 the CO2 must
be checked (follow the instructions in section 14.8) and
reset to the correct value, check the ionisation spark plug
and replace it if necessary, check the integrity of the wires
in the ionisation current electrical circuit.
If the flue gas outlet is positioned on a vertical wall it
must be protected by an anti-wind grill; if the flue gas
outlet is positioned on the roof, check that it isn’t in a
area where there is flowback, and that any anti-wind
chimney that may be provided is really effective.
Loc 21
Software error inside
control board
Replace the command and control board.
Loc 22
Software error inside
control board
Replace the command and control board.
Loc 23
Software error inside
control board
Replace the command and control board.
Loc 24
Software error inside
control board
Replace the command and control board.
Loc 25
(*)
Gas valve circuit
A - Check intervention of central heating delivery
safety thermostat;
B - Check intervention of exhaust gases temperature
safety fuse;
WARNING! If the exhaust gases temperature
safety fuse intervenes, before replacing it,
contact the appliance manufacturer in order to
avoid serious damage to the exchanger.
Loc 26
Software error inside
control board
Replace the command and control board.
Loc 27
Flame present with gas
valve closed
Replace the gas valve
Loc 28
Flame present with gas
valve closed
Replace the gas valve
Loc 29
(*)
Flue gas outlet pressure
switch circuit or external
safety devices
A - Check the connection to the external safety device;
B - Check intervention of exhaust gases differential
pressure switch;
C - Check for any possible blockage of flue gas outlet;
A - Check external safety devices connected to
terminals 103 and 104.
B - Check the pressure switch against the flue gas
outlet blockage and if necessary replace it.
C - Get rid of any possible blockages of flue gas outlet.
Loc 30
Software error inside
control board
Replace the command and control board.
Loc 31
Flame lost three times
A - Check detection electrode;
B - Check that the flue gas outlet is suitably pro
-
tected from blockages caused by gusts of wind.
C - Check for any possible recirculation of exhaust
gases
A - Try to replace detection electrode.
B - Check and if necessary get rid of any blockage in
the air intake and exhaust gases outlet ducts.
C - Look for the cause of the exhaust gases
recirculation
Loc 32
Software error inside
control board
Replace the command and control board.
Loc 33
Software error inside
control board
Replace the command and control board.
Loc 34
Software error inside
control board
Replace the command and control board.
Loc 35
Software error inside
control board
Replace the command and control board.
Loc 36
Software error inside
control board
Replace the command and control board.
Loc 37
Software error inside
control board
Replace the command and control board.
Loc 38
The flue gas sensor
does not increase in
temperature when the
burner ignites
a - Check that the flue gas sensor meets the
requirement of section 16.13.
b - Check that the flue gas sensor (parameter
1006) increases in temperature when the burner
ignites.
a - If the flue gas sensor does not meet the requirements
of section 16.13, it must be replaced.
b - If the temperature does not increase, replace the
exhaust gas temperature sensor or the command and
control board.
(*) = This error locks out all the burners