8.7 - Cleaning the condensate
conveyor siphon
For correct cleaning of the collection siphon and the
conveying of the condensate produced by combustion,
operate as follows (refer to the figures 8.5, 8.6 and 8.7):
1.- with the boiler on, open a domestic hot water cock to
maximum in a way that the burner is at maximum power
and the level of liquid present inside the siphon tank “D”
lowers (see figure 8.6);
2.- access the internal components following chapter 8.2;
3 - remove the fan burner unit following chapter 8.3;
4 - cover the electric plant and pump unit with a cloth
to protect them from any residues of water inside the
siphon to be removed.
5.- slide the support “C” outwards from the holding support;
6.- slide the tank “D” downwards, paying attention to the
fact that it is full of condensate water and this could
escape;
7.- extract the siphon outwards (see figure 8.6) paying
attention to disconnect the collection pipes of the water
coming from the upper part of the appliance and from the
air vent valve.
8.- clean the decanting tank “D”;
9.- re-mount everything in reverse order, paying attention to
the gasket “E”, which is put back in the relevant seat and
that terminal “G” is introduced correctly in the seat “H”;
10.- restore the level of liquid inside the siphon following the
procedure in chapter 6.1.2.
Figure 8.6 - Removal of the condensate collection
siphon
C
D
B
A
020002.01.027
D
E
02002.01.029
Figure 8.7 - Condensate collection siphon
H
G
F
D
E
020002.01.030
8 - MAINTENANCE
Figure 8.5 - Removal of the condensate collection
siphon