VIN_OV_FAULT_RESPONSE
[56h]
R/W Byte
Configures the VIN overvoltage fault response.
Note: The delay time is the time between restart attempts
Display format
:
-
Initial setting
:
C0 h
Range of setting and reading
:
-
Delaying time for auto recovery
:
200ms + 50ms × (bit2-0)
*1: When continuing normal operation of equal to or more than another 30 seconds of automatic-resets
about the number of times of the automatic-reset operation, it is reset.
VIN_OV_WARN_LIMIT
[57h]
R/W Word
Sets the VIN overvoltage warning threshold.
Display format
: Linear(Vin)
Initial setting
: 100 [ V ]
Range of setting and reading
: 32 - 100 [ V ]
11
1
2
In case of the extraordinary continuation, it stops output and it resumes operation
by the abnormal cancellation.
8
3
5
6
4
7
bit5-3
000
It stops output.
110 - 001
It stops if an automatic-reset is worked in the number of times ( - 6 times ) of bit5-
3 and a malfunction isn't canceled ( In the automatic-reset interval, it is prescribed
in bit2-0 ). *1
( not supported )
111
Until off operation is done, an automatic-reset is worked ( In the automatic-reset
interval, it is prescribed in bit2-0 ).
( not supported )
#
bit
7
6
5
4
3
2
1
0
Initial value
1
1
0
0
0
0
0
0
Access
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
bit
value
overview
bit7-6
00
It continues operation.
( not supported )
01
It continues operation to the delay time which is prescribed in bit2-0 and in case
of being an abnormal condition behind the delay time, too, it does the return
processing to specify in bit5-3.
( not supported )
10
It does the return processing to specify in bit5-3 after stop.
bit2-0
111 - 000
It sets the delay time of the automatic-reset.
( not supported )