RH Control Mode - Fixed
Accessible from default view by pushing <Setup> and
then twice down arrow provided control mode Fixed is
selected in the mode and reset menu.
To change parameters, push <Change>, use down
arrow to select parameter to change and push
<Select>.
Select parameter value of choice using the arrows and
then push <Save>.
”%RH Setpoint”
defines the basis for the
dehumidification.
The setpoint is not to be seen as
maximum relative humidity.
The setpoint is exceeded
by the Hysteresis Upper before the dehumidifier is
even activated.
”Hysteresis, Upper/Lower”
defines at what percentage
points, respectively above and below the setpoint that
the dehumidifier shall activate and deactivate.
”Alarm, +RH%”
defines at
what percentage point
above the activation level that the humidity alarm on
the Control Panel shall be activated.
Example:
Setpoint: 65%
Hysteresis Upper/Lower: 4% / - 4%
Alarm, +%RH: 10%
Dehumidifier activation = 65% + 4% = 69%
Dehumidifier deactivation = 65%-4%=61%
Alarm is triggered at setpoint 65% + 4 % Hysteresis
Upper + 10% Alarm =
(65+4+10)%RH= 79%RH