Installation
CTR A ES is placed and installed leveled and in a stable position so that it does not fall over and cause
damage to the machine itself, person or property.
A hose is connected to the wet air outlet in order to evacuate the moist from the room or space to
be dried. The wet air hose shall have a smooth interior surface and shall be as short as possible, no
longer than 5 meters for optimal function and performance.
In the event of problems with condensate in the wet air
hose these can, unless the hose can be shortened which is
the best solution, be improved by a further small
reduction of the dry air volume which will increase the dry
air volume. The performance will be lowered so this must
be considered and decided case by case. Another option
is to make a small hole in the wet air hose and use a
bucket for collection of the condensate.
Installation in short, main points:
1.
Place the dehumidifier where the wet air hose will reach the intended evacuation point.
Make sure that the dehumidifier is leveled and that it cannot fall over and cause damage.
2.
Connect the wet air hose and lead it to intended evacuation point (hole in the wall or
window etc. Verify that the hose is not squeezed or bent to sharply but that it will allow for
unobstructed wet air flow.
3.
Verify that the wet air throttle is fully open. For normal drying of ambient air, both dry air
throttles shall be fully open too.
4.
Connect the cable to a 1-phase, 230 V AC socket with a 10A or maximum 16A fuse. As the
machine is normally used in humid or wet spaces, the use of a ground fault circuit interrupter
is strongly recommended.
5.
Start the machine using the power switch. When the display lights up, in the first screen
presented after the start-up, push Start.
6.
Allow for the machine to warm up for a few minutes.
7.
In order to optimize the operation of the machine, push the top right button three times to
enter the Capacity menu. At the bottom of the screen, there is a wet air level indicator
showing current operation. Slowly, use the dry air throttle to adjust the flow so that the
indicator is centered on the dashed line for optimum performance.
The wet air shall always be evacuated from the
room/space to be dried.
Summary of Contents for A2 ES
Page 1: ...A2 ES A4 ES A4 ESX ADSORPTION DEHUMIDIFIERS USER MANUAL...
Page 39: ...Interface Map for CTR A2ES CTR A4 ES and CTR A ES Top Menu...
Page 40: ...Sublevels Info Statistics Info Reset Info Info Info Info Info...
Page 42: ...Create Activate Edit Edit Change...
Page 43: ...Info Change OK Info Info...
Page 44: ...Info Change OK...